CONNECTION DIAGRAM FOR FLAME ROD CURRENT
FOR FLAME RECTIFICATION SYSTEMS (DSP-5, A5)
| Microammeter | Control | |
Gas | Flame |
| |
Flame | Terminal For | ||
Rod | |||
| Flame Rod | ||
|
| ||
|
| Loadwire | |
| Flame | G | |
| Rod Assy. | ||
|
|
Figure 3 – Using a microammeter to prove adequate grounding area.
MEANS OF PROVING ADEQUATE GROUNDING AREA
The proper
NOTE:
1.Read all control data sheet supplied with this heater.
2.Check flame rod for any contact to heater parts. Flame rod must be free of any contact to heater. Contact with heater will short circuit flame rod.
3.Cracked porcelain on flame rod will short circuit sensor. Replace flame rod.
Thermostat
CAUTION TO INSTALLER
NEVER CONNECT POWERPILE GAS VALVE OR THERMOSTAT TO LINE VOLTAGE OR A TRANSFORMER.
THERMOSTAT
NOTE Do not exceed the maximum lengths listed in the
table when wiring between the Thermostat and Gas Valve with
cable not supplied by HEAT STAR.
Powerpile Thermocouple
Honeywell Q313A
| MAXIMUM |
WIRE | LENGTH |
SIZES | OF WIRE |
| CABLE |
NO 18 | 15 FEET |
NO 16 | 30 FEET |
NO 14 | 50 FEET |
|
|
Powerpile Gas Valve – Honeywell VS820
CONNECTION DIAGRAM
Factory wired
Enerco Group, Inc. | 5 | Operating Instructions and Owner’s Manual |