BASIC FLUE VENTING (Residential Only)

Venting must be in compliance with the latest edition of the National Fuel Gas Code (ANSI. Z223.1 latest edition: or the authority having jurisdiction.

Uninsulated single-wall metal pipe shall not be used outdoors in cold climates for venting of these heaters as specified by Section 7.8 of the ANSI Z223.1/NFPA 54 National Fuel Gas Code-latest edition.

For the installation of a single-wall metal pipe through an exterior combustible wall, refer to the latest edition of the National Fuel Gas Code or the authority having jurisdiction.

In regions of the country where prevailing winds are consistently higher than 40 mph, it may be necessary to terminate the vent system above the roof level.

Other venting references can be found in equipment volume of the ASHRAE Handbook.

A. SINGLE HEATER VENTING

a) Vertical Through the Roof

NOTE: For residential applications, the heater must not be connected to a separate chimney, but must be installed using the venting system as specified below.

1.When venting the heater to outside of building through a roof, use 3 inch O.D. single-wall metal pipe. This is to be constructed of galvanized sheet metal or other approved noncombustible, corrosion-resistant material as indicated by state and/or local codes.

2.A vent passing through a combustible roof shall extend through a 2-inch clearance roof thimble. Double-wall, Type B vent must be used for the portion of the vent system which passes through the roof. An approved vent cap (such as Leslie “VersaCap” Type B) must be attached to the end of the flue.

3.The maximum equivalent length of vent pipe should be carefully observed. A safety switch in the heater is designed to shut the heater off before excessive flue restriction causes bad combustion.

Minimum Equivalent Length = 5 feet of Pipe

Maximum Equivalent Length = 25 feet of Pipe

Use the following correction factors to obtain the equivalent length:

a)A horizontal run is equal to 15 feet of vent length.

b)An approved vent cap is equal to 10 feet of vent length.

c)For each elbow in the first 15 feet of run, they are equal to 10 feet of vent length.

d)For each elbow past the first 15 feet of run, they are equal to 15 feet of vent length.

EXAMPLE for an approved vent cap you have ---------

10 ft.

for a horizontal run you have -----------------

15 ft.

Your Maximum Equivalent Length is ----------------

25 ft.

4.Limit the quantity of 90° elbows to two. When vent pipe is in a horizontal run, it must rise not less than ¼ inch per foot from the start of the vent system towards the vent terminal.

5.Joints between sections of piping shall be fastened by sheet metal screws or other approved means.

The seams along the length of the piping and the joints between sections of piping should be sealed to prevent a potential leakage of flue gas into building. Use 100% RTV Silicone Rubber Adhesive sealant suitable for 500°F.

6.All portions of the vent pipe shall be supported to prevent from sagging.

7.When the vent pipe passes through areas where the ambient temperature is likely to induce condensation of the flue gasses, the vent pipe should be insulated and a condensation drain should be provided.

8.The minimum clearance to combustible materials for single- wall flue pipe shall be 6 inches. This may be reduced when the combustible material is protected as specified in the National Fuel Gas Code or the authority having jurisdiction.

9.Single-wall metal pipe shall not originate in any unoccupied attic or concealed space and shall not pass through any attic, inside wall or concealed space, or through any floor.

10.A venting system shall terminate at least 3 feet (0.9m) above any forced air inlet located within 10 feet (3.1m).

Vent Cap

(Leslie VersaCap)

Type B

 

2' Min.

 

2' Min.

 

 

2' Min.

 

(when no wall or

 

10'

(when no wall or

 

parapet exist)

 

parapet exist)

 

 

or less

 

 

 

 

 

 

 

 

Flashing

 

 

 

 

2" Clearance Thimble

 

 

 

Seal joint &

4"

 

 

 

Vent

 

 

 

annular space.

 

 

 

Dia.

Total Vent

 

 

 

¼ per ft. rise

 

 

 

Height

 

 

 

 

(5' Min.)

VERTICAL

THROUGH THE ROOF

Lateral

SINGLE HEATER VENTING

b)Vent Termination (Residential Installations)

1.The vent terminal shall terminate above the roof line so that no discharge opening is less than 2 feet (0.6m) horizontally from the roof surface. The lowest discharge opening will be no closer than the minimum height specified in the following table. These minimum heights may be used provided the vent is not less than 8 feet (2.4m) from any vertical wall or similar obstruction.

Not less than 8ft.

2ft. min.

H (Min.)

Vertical Wall

Enerco Group, Inc., Gas-Fired Low-Intensity Infrared Heater 13

Operating Instructions and Owner’s Manual

Page 13
Image 13
Enerco HST45 owner manual Basic Flue Venting Residential Only, Vertical Through the Roof, 10 ft

HST45 specifications

The Enerco HST45 is a high-efficiency heating solution that has gained popularity among consumers looking for effective solutions for their heating needs. This advanced heating system combines innovative technologies and user-friendly features to deliver optimal performance while ensuring energy savings.

One of the standout characteristics of the Enerco HST45 is its robust heating capacity. With the ability to deliver up to 45,000 BTUs, it is designed to effectively heat large spaces, making it an ideal choice for commercial applications and residential use. The unit operates on a propane or natural gas fuel system, providing flexibility in fuel choice based on user availability and preference.

The HST45 is equipped with a cutting-edge infrared heating technology. This system works by directly heating objects and surfaces in a room rather than just circulating warm air. This method results in faster and more efficient heating, reducing energy consumption and providing comfortable warmth even in large or poorly insulated spaces.

Another key feature of the Enerco HST45 is its portability. Designed with ease of movement in mind, it comes with sturdy wheels, allowing users to conveniently transport it to different locations as needed. This makes it a versatile option for construction sites, garages, workshops, and outdoor events.

Safety is also a primary consideration in the design of the HST45. The unit is equipped with an automatic shut-off feature that activates in the event of overheating, ensuring the safety of users and surroundings. Additionally, it includes a protective grill to prevent accidental contact with the heating elements, further enhancing user safety.

User-friendly controls contribute to the overall appeal of the Enerco HST45. The system features easy-to-read gauges and straightforward controls that enable users to adjust the temperature and settings according to their preferences without hassle.

Moreover, the HST45 is designed for durability and longevity, made from high-quality materials that can withstand various environmental conditions. Its sturdy construction helps ensure reliable performance through years of use, making it a worthwhile investment for anyone in need of a dependable heating solution.

In summary, the Enerco HST45 combines powerful heating capabilities, innovative infrared technology, portability, and user safety features, making it an exceptional choice for those seeking effective heating solutions. Its durability and efficiency further enhance its appeal, positioning it as a leader in portable heating systems. As energy efficiency and versatility become increasingly paramount, the Enerco HST45 stands out as a reliable and effective heating option for various applications.