Enerco HST45 Air For Combustion Residential, Outside Combustion Air Supply, System Requirements

Models: HST45

1 24
Download 24 pages 31.37 Kb
Page 16
Image 16

Vertical Venting

Air For Combustion (Residential)

If indoor combustion air is to be supplied for a tightly enclosed area, one square inch of free area opening shall be provided below the heater for each 1,000 Btu/hr of heater input.

When outside air is used, the opening below the heater shall be one square inch of free area for each 4,000 Btu/hr of heater input. In contaminated atmospheres or high humidity areas, optional outside air for combustion is recommended.

Adequate clearances around the perforated fresh air plate must be maintained at all times. In larger open areas of buildings, infiltration normally is adequate to provide air for combustion.

Direct Outside Air For Combustion (Residential)

Outside combustion air should be supplied directly to the heater when the building is subject to negative pressure or contaminants are present in the building air. These contaminates include paints, solvents, corrosive vapors or any other foreign particles that may cause damage to the heater or result in poor combustion.

Outside combustion air can be brought directly to the heater by a 3 inch diameter duct less than 25 feet long or equivalent. This is attached to a 3 inch starting collar that is fitted on inlet side of the control cabinet. An approved vent cap must be placed directly to the end of the outside combustion air inlet pipe. The combustion air inlet should be a minimum of 3 feet, either vertically or horizontally, from the flue vent termination. The air intake terminal must be located not less than one foot above grade. It is good installation practice to supply combustion air from the same pressure zone as the vent outlet.

In colder climates, where necessary, insulate the fresh air duct. Avoid locating the fresh air duct directly above the control box. Provide a capped cleanout T as necessary.

Outside Combustion Air Supply

The MHT /HSTtube heater is approved for installation with an outside air supply system. Some compounds such as halogenated hydrocarbons or other corrosive chemicals in the air can be drawn into the equipment and cause an accelerated rate of corrosion of some of the heater components. The use of such chemical compounds near the enclosure should be avoided.

IMPORTANT: If the building has a slight negative pressure or contaminants are present in the air, an outside combustion air supply to the heaters is strongly recommended.

For an outside air supply a three (3") inch O.D. single wall pipe may be attached to the heater. The duct may be up to twenty five (25') feet maximum length or two (2') feet minimum length with no more than two (2) elbows.

VERTICAL THROUGH THE ROOF

Vent Cap

(Leslie VersaCap)

 

3" Dia.

3' Min.

Single-Wall Pipe

6" Min.

Flashing

 

3" Starting Collar

¼” per ft.

 

downwards

Intake Vent

The air supply duct may have to be insulated to prevent condensation on the outer surface. The outside air terminal should be securely fastened to the outside wall by drilling four (4) holes in the outside flange; wood screws or bolts and expansion sleeves may be used to fasten terminal.

Non-Pressurized Outside Air Supply Duct

Electrical Service Installation:

System Requirements

The MHT / HST tube heater requires a grounded three-prong electrical outlet to be installed within 18”of the rear surface of the heater’s burner box. It is recommended that the outlet for the heater be ceiling-mounted and should be on a dedicated circuit. DO NOT use an electrical extension cord to operate the heater.

In order to control the heater thermostatically, it is necessary that the grounded three-prong electrical outlet be controlled with a on/ off switch or a line voltage thermostat. Please consult with an electrician or follow all local electrical codes.

Heater Rating: 120 VAC, 60Hz, Single Phase, 1 Amp

Enerco Group, Inc., Gas-Fired Low-Intensity Infrar ed Heater

16

Operating Instructions and Owner’s Manual

Page 16
Image 16
Enerco HST45 owner manual Air For Combustion Residential, Outside Combustion Air Supply, Electrical Service Installation