Pressure Testing Heater Gas Connections:
1.Make sure that the heater supply piping sys- tem is connected and has been leak tested as described above.
2.Make sure control knob of heater is in OFF position.
3.Open equipment shutoff valve (see figure 13).
4.Open propane/LP supply valve.
5.Check all joints from equipment shutoff valve to control valve (see figure 14). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
6.Correct all leaks at once.
7.Light heater (see Operating Your Heater, pages 11 and 12 for thermostat models or pages 9 and 10 for
8.Turn off heater (see To Turn OFF Gas to Appli- ance, page 12 for thermostat models and page 11 for
9.Replace lower front panel.
Open
Equipment | Closed |
Shutoff Valve |
|
Figure 13
Figure 14
Control Valve
Gas Meter
Equipment
Shutoff Valve
ELECTRICAL WIRING DIAGRAM:
Figure 15
If any original wiring as supplied with the heater must be replaced, it must be replaced with type AWG 105oC wire or its equivalent except as indicated.
WARNING: Electrical Grounding Instructions: This heater is equipped with a
OPERATING YOUR HEATER
NON-THERMOSTAT MODELS
IR10LP / BF10LP
FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing prop- erty damage, personal injury or loss of life.
A.This appliance has a pilot that must be lighted by hand. When lighting the pilot, follow these instructions exactly.
B.BEFORE LIGHTING smell all around the appli- ance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use any phone in your building.
•Immediately call you gas supplier from a neigh- bor’s phone. Follow the gas supplier’s instruc- tions.
•If you can not reach your gas supplier, call the fire department.
Unvented Liquid Propane Fired Room Heater | 9 | Installation Instructions and Owner’s Manual |