Enerco MHU 45, MHU 75 D - Horizontal Venting - Commercial, E - Horizontal Venting - Residential

Models: MHU 45 MHU 75

1 16
Download 16 pages 26.17 Kb
Page 7
Image 7
D – HORIZONTAL VENTING – COMMERCIAL

5.Vent termination must be a minimum of 4' (1.2m) below or 4’ (1.2m) horizontally from any soffit vent or under-eave vent.

6.Vent must be a minimum of 6' from an inside corner formed by two exterior walls. If possible, leave a 10' clearance.

7.Vent termination must be a minimum of 10' (3m) from any forced air inlet (includes fresh air inlet for other appliances, such as a dryer).

8.When termination is routed through an exterior combustible wall the vent must be supported using a listed clearance thimble. Where local authorities permit, a single section of type B-1 vent pipe may be used as an alternative to the thimble. When using a type B-1 vent termination use the clearances specified by the vent manufacturer. Seal the connection between the single wall and double wall pipes and the annular space of the double wall pipe as shown in figure 2. Inside edge of vent termination tee must be at least 12 inches from outside wall as shown in figure 3 .

9.For horizontal venting, the vent pipe shall be supported with hangers no more than 3ft. (1m) apart to prevent movement after installation.

D – HORIZONTAL VENTING – COMMERCIAL

1.Horizontal commercial installations are for buildings which are not attached to living spaces. The vent may be single wall vent material installed according to the sections

Venting A - General Recommendations and Requirements and C - Horizontal Venting General and

D - Horizontal Venting - Commercial. Refer to figure 3.

2.The vent pipe diameter for horizontal commercial installations shall be 4" (101mm) on the 45 and 75units. In all cases a flue transition piece (supplied) is required to fit over the outlet of the induced draft assembly on the appliance.

3.Refer to table 2 for maximum vent connector lengths.

4.Select a wall termination point that will maintain ¼” rise per foot slope of horizontal run of vent pipe. The vent may be single wall material minimum 26 GSG (0.46mm) galvanized steel or equivalent grade stainless steel. Seal single wall vent material according to the section A - General

Recommendations and Requirements.

5.For upward sloped vent a condensate tee and drain must be installed within the first 5’ (1.5m) from the unit heater to protect the appliance. If a flexible condensate drain line is used, the drain line must include a loop entering the structure. If the unit is shut down for an extended period of time and will be exposed to sub-freezing temperatures, the condensate may freeze.

E – HORIZONTAL VENTING – RESIDENTIAL

1.For horizontal residential installations these units are certified as Category I appliances. The vent may be single wall material minimum 25 GSG (0.46mm) galvanized steel or equivalent grade stainless steel. Venting A - General Recommendations and Requirements and C - Horizontal Venting General and E - Horizontal Venting - Residential. Refer to figure 6 .

2.The vent pipe diameter for horizontal residential installations shall be 4" (101mm) on both 45 and 75 units. A standard vent transition is required at unit in addition to the transition supplied with the unit.

3.The maximum vent length is 5’ (1.5m) plus one 90-degree elbow.

4.The vent must maintain a ¼” rise per foot of slope upwards toward the termination.

CONDENSATE DRAIN THROUGH TEE PIPE AND DRAIN LOOP

UPWARD SLOPE ON HORIZONTAL VENT-COMMERCIAL INSTALLATION

MAY BE SINGLE WALL (26 GSG) GALV. OR EQUIV. STAINLESS STEEL SEALED ACCORDING TO THESE INSTALLATION INSTRUCITONS. SLOPE: + 1/4 INCH FOR 1 FOOT RUN MINUMUM.

 

FLUE TRANSITION

 

(PROVIDED)

 

LISTED THIMBLE

 

THROUGH COMBUSTIBLE

 

WALL

INDUCED DRAFT BLOWER

 

NOTE - MINIMUM HORIZONTAL LENGHT 3 FT. (914MM),

 

NOT INCLUDING CAP FOR TERMINATION. REFER TO

DRAIN LOOP WITH WATER

TABLE 2 FOR MAXIMUM LENGTH AND NUMBER OF

TRAP (TO CONDENSATE DRAIN)

ELBOWS.

 

12 INCHES MIN.

(30.5 CM)

VENT TERMINATION

CAP

12” (30.5 CM)

MINIMUM ABOVE ALL HIGHEST SNOWFALL

COMMON VENTING NOT ALLOWED WHEN HORIZONTALLY VENTING THE UNIT HEATER

FIGURE 3

Enerco Compact Unit Heater

7

Operating Instructions and Owner’s Manual

Page 7
Image 7
Enerco MHU 45, MHU 75 owner manual D - Horizontal Venting - Commercial, E - Horizontal Venting - Residential