Enerco MHU 45, MHU 75 owner manual Electrical Connections, Figure Gas Supply Connection

Models: MHU 45 MHU 75

1 16
Download 16 pages 26.17 Kb
Page 9
Image 9
FIGURE 7

 

LINE VOLTAGE FIELD WIRING

 

UNIT

L1

BLACK

 

BLACK

N

WHITE

 

 

WHITE

EQUIPMENT

GROUND

BLACK WIRE WITH WHITE TAPE OR

WHITE WIRE WITHOUT TAPE

FIGURE 7

GAS SUPPLY CONNECTION

 

MANUAL

 

MAIN SHUT-OFF VALVE

 

(FURNISHED BY INSTALLER)

GROUNDED

 

JOINT UNION

 

1/8 NPT

GAS FLOW

PLUGGED TAP

 

DRIP LEG

 

FIGURE 8

GAS SUPPLY TO UNIT HEATER

MANUAL MAIN SHUT-OFF

 

VALVE WILL NOT HOLD

 

NORMAL TEST PRESSURE

ISOLATE

 

GAS VALVE

CAP

 

UNIT HEATER

 

FIGURE 9

5.Test for spillage at the draft hood relief opening after five minutes of main burner operation. Use the flame of a matchor candle, or smoke from a cigarette, cigar, or pipe.

6.After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous condition of use.

7.If improper venting is observed during any of the above tests, the common venting system must be corrected. The common venting system should be resized to approach the minimum size as determined by using the appropriate tables in Appendix G in the current standards of the National FuelGas Code, ANSI Z223-1 in the U.S.A. and the appropriate Category I Natural Gas and Propane appliances venting sizing tables in the current standards of the CSA B149.1 Natural Gas and Propane Installation Code in Canada.

NOTE Local codes may supersede any of the above provisions.

ELECTRICAL CONNECTIONS

NOTE The MHU/HSU series unit heaters use a direct spark ignition system. There is no pilot necessary as the spark lights the main burner as the gas valve is turned on. The direct spark ignition

FIGURE 8 WARNING

Electric shock hazard. Can cause injury or death. Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the furnace and to replace any part of the control system and any gas control which has been under water.

ELECTRICAL CONNECTIONS WARNING

Danger of explosion. Can cause injury or product or property damage. If over- heating occurs or if gas supply fails to shut off, shut off the manual gas valve to the appliance before shutting off electrical supply.

Manual background WARNING

Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.

Manual background WARNING

Danger of explosion and fire. Can cause injury or product or property damage. You must follow these instructions exactly.

Enerco Compact Unit Heater

9

Operating Instructions and Owner’s Manual

Page 9
Image 9
Enerco MHU 45, MHU 75 owner manual Electrical Connections, Figure Gas Supply Connection, Figure Gas Supply To Unit Heater