WARNING: This appliance requires a 3/8” NPT (National Pipe Thread) inlet connection to the pressure regulator. Use of floor mounting feet will require you to use a 3/8 NPT street elbow to make gas connection.­

CAUTION: Never connect heater to private (non-utili- ty) gas well. This gas is commonly known as well-head gas.­

IMPORTANT: Check your gas line pressure before con- necting heater to gas line. Gas line pressure must be no greater than 14 inches of water. If gas line pressure is higher, heater regulator damage could occur.

CAUTION: Use only new black iron or steel pipe. Internally-tinned copper tubing may be used in cer- tain areas. Check your local codes. Use pipe of larger enough diameter to allow proper gas volume to heater. If pipe is too small, undue loss of pressure will occur.­

Installation must include an equipment shutoff valve, union and plugged 1/8” NPT tap. Locate NPT tap within reach of test gauge hookup. NPT tap must be upstream from heater (see figure 12).

taminants. This keeps them from going into heater. If sediment trap is not installed or is installed improperly, heater may not run correctly.

IMPORTANT: Hold pressure regulator with wrench when connecting it to gas piping and/or fittings.

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.­

WARNING: Never use an open flame to check for a gas leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.­

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM

Test pressure in Excess of ½ psig (3.5kPa)

1.

Disconnect appliance with its appliance main

 

gas valve (control valve) and equipment shutoff

 

valve from gas supply piping system. Pressures

 

in excess of ½ psig will damage heater regula-

 

tor.

2.

Cap off open end of gas pipe where equipment

3/8” NPT Pipe Nipple

Ground Joint Union

Equipment

Shutoff Valve

From Gas Meter (4” W.C. to 10.5” W.C. Pressure)

3” Minimum

Pressure

Regulator

Heater

Cabinet

Test Gauge

Connection

Tee Joint

Reducer Bushing to 1/8” NPT

1/8” NPT Plug Tap

Tee Joint

Pipe Nipple SedimentTrap

Cap

 

shutoff valve was connected.

3.

Pressurize supply piping system by either using

 

compressed air or opening main gas valve on

 

or near gas meter.

4.

Check all connections and joints in gas supply

 

piping system. Apply mixture of liquid soap and

 

water to gas joints. Bubbles forming show a

 

leak.

5.

Correct all leaks at once.

6.

Depressurize and relieve pressure in supply

 

piping system.

7.

Reconnect heater and equipment shutoff valve

 

to gas supply.

8.

Reconnected fittings must be checked for leaks

 

in next section.

Figure 12

*A CSA/AGA certified equipment shutoff valve with 1/8” NPT tap is an acceptable alternative to test gauge connection. Purchase the CSA/AGA certified equipment shutoff valve from your dealer. See Accessories, page 17.

IMPORTANT: Install an equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.

Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater fuel train.

CAUTION: Use pipe joint sealant that is resistant to natural gas

Install sediment trap in supply line as shown in figure

12.Locate sediment trap where it is within reach for cleaning. A sediment trap traps moisture and con-

Test Pressure Equal To or Less Than ½ psig (3.5 kPa)

1.Close equipment shutoff valve (see figure 13).

2.Pressurize supply piping system by either using compressed air or opening main gas valve on or near gas meter.

3.Check all joints from the gas meter to equip- ment shutoff valve (see figure 14). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

5.Depressurize and relieve pressure from supply piping system.

Unvented Natural Gas Fired Room Heater

8

Installation Instructions and Owner’s Manual

Page 8
Image 8
Enerco TSIR10NG, TSIR20NGT Test pressure in Excess of ½ psig 3.5kPa, Test Pressure Equal To or Less Than ½ psig 3.5 kPa

MHBF10NG, HSIR20NGT, HSBF10NG, MHIR10NG, MHIR20NGT specifications

The Enerco HSIR10NG, TSIR10NG, TSBF10NG, TSIR20NGT, and MHBF6NG are a line of innovative heating solutions designed to meet various heating needs in both residential and commercial applications. Each model is engineered with advanced technologies and features that prioritize efficiency, performance, and user convenience.

The HSIR10NG is a high-efficiency infrared heater that operates on natural gas. It provides powerful heating with minimal energy consumption, utilizing infrared technology to warm objects and people directly rather than just the surrounding air. This results in faster heating and lower energy costs, making it an ideal choice for garages, workshops, or outdoor spaces.

Following closely is the TSIR10NG, another natural gas infrared heater known for its compact design and efficiency. This model features a state-of-the-art burner design that maximizes heat output while ensuring low emissions. The TSIR10NG is particularly suited for smaller spaces, providing targeted heating where it is needed most. It can easily be mounted on walls or ceilings, offering versatility in installation options.

The TSBF10NG is a dual-fuel infrared heater, allowing users to switch between natural gas and propane as needed. This flexibility makes it suitable for various environments and user preferences. The heater's robust construction ensures durability, while its adjustable heating levels allow for customized comfort.

For larger areas, the TSIR20NGT offers an enhanced heating capacity with similar infrared technology. This model is ideal for industrial or commercial spaces requiring efficient heating. With its advanced thermostat controls, users can maintain a consistent temperature while benefiting from lower operational costs.

Lastly, the MHBF6NG is a portable heating solution designed for versatility and convenience. This compact model is perfect for temporary heating needs, featuring an easy-to-use design that allows for quick setup and relocation. Its propane compatibility makes it a popular choice for outdoor events, workshops, or emergency heating situations.

Each model is equipped with advanced safety features, including automatic shutoff mechanisms and durable heat-resistant materials, ensuring peace of mind during operation. The Enerco line is engineered not only for performance but also for ease of maintenance, making them reliable options for users seeking efficient heating solutions. Overall, Enerco's HSIR10NG, TSIR10NG, TSBF10NG, TSIR20NGT, and MHBF6NG provide a range of effective heating options tailored to diverse environments and user needs, combining innovation with practical functionality.