Enviro EG-40 owner manual Venting Fireplace Inserts

Models: EG-40

1 17
Download 17 pages 3.62 Kb
Page 7
Image 7
Figure 7

5. VENTING

WARNING; THIS APPLIANCE HAS BEEN DESIGNED TO OPERATE BY DRAWING COMBUSTION AIR AND DILUTION AIR FROM THE ROOM. IT IS ALSO DESIGNED TO DRAW ROOM AIR FOR PROPER HEAT CIRCULATION FROM THE SIDES OF THE UNIT. BLOCKING OR MODIFYING THE LOUVERS IN ANY WAY CAN CREATE HAZARDOUS SITUATIONS, EITHER THROUGH POOR VENTING OR BY OVERHEATING. IT IS IMPORTANT THAT THIS UNIT HAS SUFFICIENT AIR CIRCULATION FOR PROPER VENTING AND COMBUSTION. PROVISIONS MUST BE MADE FOR THE SUPPLY OF ADEQUATE COMBUSTION AND VENTILATION AIR. THESE OPENINGS MUST NOT BE BLOCKED.

THE APPLIANCE MUST NOT BE CONNECTED TO A

CHIMNEY FLUE SERVICING A SEPARATE SOLID FUEL

BURNING APPLIANCE.

VENTING FIREPLACE INSERTS

The ENVIROGAS insert may be installed and vented into any solid fuel fireplace that has been installed in accordance with the National, Provincial/State and local building codes and has been constructed of non-combustible materials.

An listed 4" chimney liner, seal plate, and rain cap must be installed, to ensure a tight seal, top performance, safety and efficiency. Carefully follow the chimney manufacturer’s instructions that accompany the liner kit.

Measure the height of the chimney before hand and purchase the appropriate kit. Never attempt to over stretch a flexible liner to accommodate the height of the chimney.

Install a seal plate to prevent leakage of room air through chimney. If the chimney is not sealed damage may occur to the appliance.

Any flue damper must be removed or blocked permanently in the open position.

The chimney must be clean, in good working order and constructed out of non-combustible materials.

Make sure that all chimney clean outs are tightly fitting and will not permit air to leak into the chimney.

Remove the vent collar plate from the top of the insert and connect it securely with at least 3 sheet metal screws and a 4"

hose clamp. Check for any tears in the liner at this point. (See also Assembly and Installation Instructions section 3.)

IMPORTANT: Replace the screw that holds the vent collar plate in it's approved position.

The draft hood must be in the same pressure zone as the air inlet.

To inspect draft from the front of the unit, open right side hinged flap. Locate 3/8” tube and check for draft using smoke or magnehelic gauge. A vacuum will indicate proper drafting.

7

Page 7
Image 7
Enviro EG-40 owner manual Venting Fireplace Inserts