11. ELECTRICAL REQUIREMENTS
The ENVIROGAS
The appliance when installed, must be electrically connected and grounded in accordance with local codes or in the absence of local codes, with the current CSA C22.1 CANADIAN ELECTRICAL CODE Part 1,
SAFETY STANDARDS FOR ELECTRICAL INSTALLATIONS, OR THE NATIONAL ELECTRICAL CODE ANSI / NFPA 70 in the USA.
NOTE:
•Operation of the fan increases the efficiency and heat output of the unit.
•This unit is able to operate with a millivolt rated thermostat.
•To connect the thermostat use the two- (2) purple wires in the harness. Install the thermostat in series with the purple wires.
CAUTION Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
WARNING; Electrical grounding instructions. This appliance is equipped with a
INSTALLING REMOTE THERMOSTAT OR WALL SWITCH
RECOMMENDED WIRE SIZE for thermostat installation: 18 gauge, 2 wire solid core, Low Voltage wire. (Bell wire)
1.Install the 18 Gauge wire supplied to the two terminals on the thermostat or remote wall switch.
2.Connect the other end of the wire to the gas valve using the two outside terminals on the front of the gas valve. Use the terminals marked (TP/TH and TH).
RECOMMENDED MAXIMUM LEAD LENGTH (TWO WIRE)
WHEN USING WALL THERMOSTAT
WIRE SIZE | MAXIMUM LENGTH |
14 GAUGE | 100 FEET |
16 GAUGE | 64 FEET |
18 GAUGE | 40 FEET |
20 GAUGE | 18 FEET |
13