Trouble Shooting
Problem | Possible Cause | Solution | |
|
|
| |
The main burner | The gas valve may not be on. | • Check that the gas control knob is in the “ON” position. | |
does not ignite |
|
| |
Thermostat is not calling for | • Adjust the thermostat several degrees above ambient temperature. | ||
when called for. | heat. |
| |
|
| ||
|
|
| |
| Problem with gas valve. | • Use a DC voltmeter to measure the voltage across the TPTH and | |
|
| TP terminals. Main operator voltage: Open circuit ≥ 325mV Closed | |
|
| circuit ≥ 100mV | |
|
| • If voltage is not present, check the control circuit for proper | |
|
| operation. | |
|
| • If proper control system voltage is present, replace the gas control. | |
|
|
| |
Spark will not | Defective piezo ignitor. | • Check connections to ignitor. | |
light the pilot |
| • If ignitor connections are good but no spark, replace ignitor. | |
after repeatedly |
|
| |
Broken spark electrode. | • Check for broken ceramic insulation, replace electrode if broken. | ||
pressing the | |||
|
| ||
Misaligned spark electrode. | • If spark is not arcing from electrode to pilot, loosen the screws on the | ||
spark ignitor. | |||
|
| pilot base adjust and tighten. | |
Pilot will not | Problem with thermocouple | • Check for proper connection of the thermocouple to the rear of the | |
remain lit. | circuit. | valve. If loose, fully tighten. | |
|
| • Check pilot for full flame impingement around thermocouple. If flame | |
|
| is too small, check gas pressure, adjust pilot rate screw, check pilot | |
|
| head for damage. | |
|
| • Check thermocouple voltage at valve. It must be greater than 5 mV. | |
|
| If low, replace thermocouple. | |
|
|
| |
| Air in gas line (pilot dies while | • Bleed line. | |
| knob is depressed). | • Check gas line pressure. | |
|
| • Contact dealer. | |
|
|
| |
Burners will not | Problem with thermopile | • Check gas line pressure . | |
remain lit. | circuit. | • Check for flame impingement on thermopile. If low, see “Pilot will not | |
|
| remain lit”. | |
|
| • Check thermopile for minimum of 300 mV when burner is switched | |
|
| on. | |
|
| • Check wiring to thermostat for breaks. | |
|
| BV ONLY: Check for spillage at draft hood that may trip spill switch | |
|
|
| |
Flame lifting | Leak in vent pipe | • Check for leaks in vent connections. | |
|
|
| |
| Improper vent configuration | • Check vent configuration with manual. | |
|
|
| |
| Terminal may be recirculating | • Check to see if terminal is on correctly. | |
| flue gases | • May need to install high wind termination cap. | |
|
| • Contact dealer. | |
|
|
| |
Glass fogs up | Normal Condition: after the appliance warms up the glass will clear. | ||
| **Due to additives in gas, glass may get hazy during operation** Clean as needed. | ||
|
|
| |
Blue Flames | Normal during start up: flames will yellow as the fireplace heats up. | ||
|
|
| |
Flames are | Flame impingement | • Check log positioning. | |
burning “dirty” or |
| • Increase primary air by opening the venturi shutter and/or by | |
sooting |
| opening the vent restrictor. | |
|
| See also “Burners will not remain lit.” | |
|
|
| |
Remote control | Problem with the remote | • One or more of the batteries are dead. See remote control | |
doesn’t work |
| instructions. | |
|
|
| |
| Problem with fireplace | • The on/off switch is turned to OFF. | |
|
| • The gas control valve is turned to PILOT or OFF. | |
|
| • The pilot has gone out. | |
|
|
| |
BV ONLY: | • Air tight house. | • Supply make up air to the unit. | |
Insufficient air | • A vacuum in room due to |
| |
for combustion | other |
| |
|
|
|
22