Control — MLS Switcher

Control — MLS Switcher

MLC/IR

A B C

Rear Panel

 

MLC/IR port

 

on MLS Switcher

 

Heat Shrink Over Ground or Drain Wires

NOTES:

• You must connect a ground wire between the MLC and MLS.

If you use cable that has a drain wire, tie the drain wire to ground at both ends.

Ground (MLC/IR)

BReceive (Rx) • You must connect a ground wire between the MLC and MLS. Transmit (Tx) B

A Transmit (Tx) Bottom Receive (Rx) A

 

 

 

S

 

 

 

 

 

S

 

 

 

 

 

 

Rx

Tx

 

 

 

 

 

 

 

Bottom

 

 

 

GROUND

 

 

 

 

GROUND

 

GROUND GROUND +12VIN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B

 

MLC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Panel

 

 

 

B

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MLS

 

PWR

 

IR/SERIAL

OUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS-232

12V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power

Ground

12 VDC

 

(ridged)

(smooth)

Power Input

• Connect to 12 VDC, 1 A power supply.

Check the polarity of the power supply wires before connecting it to the MLC.

Front panel buttons light when the

 

MLC receives power.

3/16"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(5 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ground (

)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+12 VDC Input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External

 

S

 

GROUND

 

S

 

 

GROUND

Rx

 

 

Tx

GROUND GROUND +12VIN

 

(12 VDC, 1 A max.)

Bottom

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Supply

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

B

 

 

 

 

 

 

Panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MLS

 

 

PWR

 

 

IR/SERIAL OUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS-232

 

12V

 

Ground all devices.

MLS Switcher RS-232 Port

Select RS-232 protocol via software or SIS command. Signals are bidirectional, ±5 V.

RS-232 default protocol:

• 9600 baud

• 8 data bits • 1 stop bit

• no parity

• no flow control

Control — LAN (Ethernet)

MAC Address

MAC: 00-05-A6-XX-XX-XX(on top, and on front panel)

S/N:

Straight-through Cable

(for connection to a switch, hub, or router)

 

End 1

 

End 2

Pin

Wire Color

Pin

Wire Color

1

white-orange

1

white-orange

2

orange

2

orange

3

white-green

3

white-green

4

blue

4

blue

5

white-blue

5

white-blue

6

green

6

green

7

white-brown

7

white-brown

8

brown

8

brown

Both ends use the TIA/EIA T568A wiring standard.

 

 

 

 

Pins:

Crossover Cable

12345678

 

 

 

 

 

 

 

 

 

(for direct connection to a PC)

RJ-45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

End 1

End 2

Connector

 

 

 

 

 

 

 

 

Pin Wire Color

Pin Wire Color

 

 

 

 

 

 

 

 

 

Left Panel

Link LED:

Lights to indicate Panel a network connection.

Activity LED: Blinks to indicate data is being sent or received.

Ethernet (LAN)

Connect to an Ethernet network with a straight through cable. This port must be configured.

Default protocol:

MLC IP address: 192.168.254.254

Gateway IP address: 0.0.0.0

Subnet mask: 255.255.0.0

DHCP: off

Link speed and duplex level: autodetected

NOTE: You must use this LAN port to set up the MLC and upload GC configuration

1

white-orange

1

white-green

 

2

orange

2

green

 

3

white-green

3

white-orange

 

4

blue

4

blue

 

5

white-blue

5

white-blue

 

6

green

6

orange

PC

7

white-brown

7

white-brown

 

8

brown

8

brown

 

Wire end 1 following the TIA/EIA T568A wiring standard, wire end 2 with the T568B wiring standard.

TCP/IP

Network

Insert Twisted

Pair Wires

files and firmware.

All configuration can be performed via this port.

3

Page 3
Image 3