System Setup

SYSTEM SETUP:

Figure 1 shows a typical oil-fired appliance and the expected ranges of several readings taken at various locations in the system. Note: If a vent pipe reducer is required, use a smooth walled gradual reducer. Place it at the venter inlet as shown in Figure 1.

1.Set the choke plate in the power venter, or extension kit, to its full open position. Set the draft control adjustment weight to its midpoint position.

2.Adjust the thermostat so that the unit will run continuously. Allow the unit to operate for 5 to 10 minutes to ensure stack temperature stabilization.

3.Find out the manufacturer’s recommended over-fire or breeching draft. Close the choke plate on the SWG until the draft above the draft control reads approximately 0.04” w.c. greater than the recommended breeching draft. Example: If the appliance manufacturer recommends a 0.02” breech draft, adjust the choke plate to get an approximate 0.06” draft above the draft control.

4.Adjust the barometric draft control to obtain the manufacturer’s recommended draft over-fire or at the breech. The draft control gate should be open approximately half its full swing during normal operation. This allows the gate to swing open or closed depending on changes in atmospheric pressure or operating conditions.

5.If the proper draft cannot be obtained at the breech or if the gate does not open as described, then adjust the choke plate in the SWG to reduce or increase the airflow. Re-adjust the draft control to obtain the required draft, since moving the choke plate will change the system draft.

Procedure for adjusting the pressure switch

Turn pressure switch adjustment clockwise until the burner quits.

Turn counter-clockwise slowly until the burner starts.

Turn an additional 1/4 to 1/2 turn counter-clockwise.

Note: Every installation will require unique pressure switch adjustment.

Figure 1

12

Page 11
Image 11
Field Controls Oil Venting Systems manual System Setup, Procedure for adjusting the pressure switch

Oil Venting Systems specifications

Field Controls Oil Venting Systems are engineered to enhance the efficiency and safety of oil heating applications while ensuring environmental compliance. These systems are designed to facilitate the venting of combustion gases, preventing the buildup of harmful substances and maintaining optimal performance of oil-fueled heating appliances.

A standout feature of Field Controls Oil Venting Systems is their adaptability. They can be seamlessly integrated with a variety of oil-fired heating units, including furnaces and boilers. This versatility allows homeowners and businesses to upgrade or replace their existing venting systems with minimal hassle, leading to improved energy efficiency and reduced operational costs.

The technology that underpins these venting systems is designed to optimize airflow and minimize pressure drop, allowing for efficient exhaust of combustion gases. Field Controls employs advanced materials that are resistant to corrosive gases, ensuring a longer lifespan and reduced maintenance requirements. Additionally, their systems utilize a unique multi-hinge design, which enhances flexibility during installation, ensuring a perfect fit in a diverse range of configurations.

Field Controls also focuses on safety with features such as backdraft dampers and safety switches. These elements prevent backflow of exhaust gases into the living space, providing peace of mind for users. The systems are rigorously tested to comply with national safety standards, ensuring a reliable and secure installation for residential and commercial applications alike.

Moreover, Field Controls Oil Venting Systems prioritize efficiency by optimizing the venting process. This results in reduced energy consumption and lower emissions, aligning with modern environmental standards and helping users transition to more sustainable heating options.

In summary, Field Controls Oil Venting Systems represent a robust solution for oil heating applications, combining safety, efficiency, and adaptability. With their innovative design and commitment to quality, they provide users with a reliable means to manage oil venting, ensuring both comfort and compliance with environmental regulations. By investing in a Field Controls system, customers can enhance their heating systems while contributing to a cleaner and more efficient future.