Field Controls SK-1 manual Special Venting Application Installation Sheet

Models: SK-1

1 12
Download 12 pages 41.18 Kb
Page 4
Image 4
SPECIAL VENTING APPLICATION INSTALLATION SHEET
Figure 4
Figure 5

SPECIAL VENTING APPLICATION INSTALLATION SHEET

This sheet covers the requirements for installation of the Starkap™ for use with attached buildings designed for the purpose of housing heating equipment outside of the living space of the structure. These requirements are based on A.G.A. test reports C-FT-5-90, C-FT-8-90, FT-C-12-93 AND FT-C-13-93. See Figure 4 and 5.

1.The maximum gas heating appliance (or multiple appliances ) up to 250,000 BTU/HR input.

2. Each appliance in the building MUST have its own separate vertical vent and Starkap™.

3.The connecting wall between the attached building and the main structure MUST be sealed to prevent flow into the main structure. Example: Attached garages must be

sealed by lining ceiling and any wall adjacent to the living space with 1/2" thick gypsum board or equivalent. Openings from an attached garage directly into a room used for sleeping purposes shall not be permitted. Other openings between the garage and residence shall be equipped with either solid wood doors not less than 1-3/8" in thickness or 20-minute fire-rated doors, or equivalent.

4. Two make up/combustion air openings into the outside building shall be installed. Size of the openings shall be 10 inch by 10 inch or based on 1 sq. inch per 4000 BTU/HR.

5. Termination location shall have a 4 ft. 9 in. center line distance from any vertical wall up to 250,000 BTU/HR.

Termination location for up to 40,000 BTU/HR water heaters shall be a minimum 1 ft. 6 in. center line distance from any vertical wall. A minimum height of 12 inches shall be maintained above the roof.

6.The vent termination shall be located at least 4 feet from any window or opening into the main building structure.

Page 4

Page 4
Image 4
Field Controls SK-1 manual Special Venting Application Installation Sheet