FieldServer FS-8700-03 DF1 instruction manual Configuring the FieldServer as a DF1 Server

Models: FS-8700-03 DF1

1 16
Download 16 pages 21.06 Kb
Page 10
Image 10
5.Configuring the FieldServer as a DF1 Server

FS-8700-03 DF1 Driver Manual

Page 10 of 16

5.Configuring the FieldServer as a DF1 Server

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” files on the driver diskette).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a DF1 Client.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for DF1 communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the Clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

5.1.Server Side Connection Descriptions

 

Section Title

 

 

 

 

 

Connections

 

 

 

 

 

Column Title

 

Function

 

Legal Values

 

Port

 

Specify which port the device is connected

 

P1-P86

 

 

 

to the FieldServer

 

 

 

Baud*

 

Specify baud rate

 

300 to 115200; 9600

 

Parity*

 

Specify parity

 

Even, Odd, None

 

Data_Bits*

 

Specify data bits

8

 

Handshaking*7

 

Specify hardware handshaking

 

RTS, RTS/CTS, None

 

Protocol

 

Specify protocol used

 

DF1_FD, DF1_HD_MASTER,

 

 

 

DF1_HD_SLAVE

 

 

 

 

 

 

 

 

 

 

 

Example

//Server Side Connections

Ports,

 

 

Port,

 

Protocol

P1,

 

DF1_FD

6Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction

manual for details of the ports available on specific hardware.

7 Handshaking is not supported, only the enabling of the RTS/CTS lines

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 10
Image 10
FieldServer FS-8700-03 DF1 Configuring the FieldServer as a DF1 Server, Server Side Connection Descriptions