FieldServer FS-8700-03 DF1 Appendix A. Driver Notes Appendix A.1. Continuous Map Descriptors

Models: FS-8700-03 DF1

1 16
Download 16 pages 21.06 Kb
Page 14
Image 14
Appendix A. Driver Notes

FS-8700-03 DF1 Driver ManualPage 14 of 16

Appendix A. Driver Notes

Appendix A.1. Continuous Map Descriptors

RS View has been known to crash if it tries to read a Server mapping that is discontinuous.

e.g.

Server map 1:

N21:

0-31

 

Server map 2:

N21:

32-100

This will panic the FieldServer and crash RS view as the DF1 will attempt to map N21: 0-100

If set up as:

Server Map 1: N21: 0-100 No problems are experienced

Appendix A.2. Checksum

You can now specify a checksum parameter for the serial connection. The heading keyword is "Checksum" and the possible values are

1) BCC or 2) CRC-16

If nothing is specified it defaults to BCC.

Example:

Connections

 

 

 

Port,

Baud,

Protocol,

Checksum

P1,

9600,

DF1_FD,

CRC-16

The Checksum is valid for both DF1_FD and DF1_HD.

Appendix A.3. Command Support

The following commands are supported by the FieldServer for the various PLC types:

 

PLC_Type

 

 

File_Type

 

 

FNC

 

 

Read

 

 

FNC

 

 

Write

 

 

Typical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

1

 

 

Range Read

0

 

Range Write

N7: 3, L5

 

PLC3

 

F

1

 

 

Range Read

0

 

Range Write

F12: 3, L5

 

 

 

 

B

1

 

 

Range Read

2

 

Bit Write

 

B3/4: 5, l5

 

 

 

 

N

1

 

 

Range Read

0

 

Range Write

N7: 3 , L5

 

PLC5

 

F

1

 

 

Range Read

67

 

Typed Write

F12: 3, L5

 

 

 

 

B

1

 

 

Range Read

26

 

Read Modify Write

B3/4: 5, L5

 

 

 

 

N

 

A2/A1

 

Protected Typed

 

AA

 

Protected Typed

 

N7: 3, L5

 

 

 

 

 

 

 

 

 

 

Logical Read

 

 

 

 

Logical Write

 

 

 

 

 

 

 

F

 

A2/A1

 

Protected Typed

 

AA

 

Protected Typed

 

B3/4: 5, L7

 

 

 

 

 

 

Logical Read

 

 

Logical Write

 

 

SLC5

 

B

 

A2/A1

 

Protected Typed

 

AB

 

Protected Typed

 

B3/4: 5, L8

 

 

 

 

Logical Read

 

 

Logical Write

 

 

 

 

 

I

 

A2/A1

 

Protected Typed

-

 

-

 

 

I: 13, L5

 

 

 

 

 

 

 

 

 

 

Logical Read

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

A2/A1

 

Protected Typed

-

 

-

 

 

O: 13, L5

 

 

 

 

 

 

Logical Read

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 14
Image 14
FieldServer FS-8700-03 DF1 Appendix A. Driver Notes Appendix A.1. Continuous Map Descriptors, Appendix A.2. Checksum