FS-8700-122 X30 Profibus DP Master Manual

Page 13 of 16

7)Select the first slave device, right-click on the Slot 1 line and choose Module selection. Now you have to add I/O modules up to the total number of bytes or words that will be transferred with this slave as set up in the config.csv file. For Example, for the Map Descriptor for Slave1 using 50 Words In and Out, you would choose the following modules:

8) Continue selecting other Slaves and adding modules for them as well.

Important Note: Changing of Input and Output Addresses are not allowed. All addresses must be contiguous for the X30 Profibus to work correctly.

9)Select Online-> Driver selection and on the serial Tab, choose the serial port on the PC connected to the X30 by clicking on Configure-> Configure path.

10)Make sure the X30 FieldServer is running and you’ve downloaded a matching configuration file to it with Node and Map Descriptors for each slave you have just configured Make sure you can connect with Ruinet to the X30 and there are no configuration errors.

11)Choose Online-> Download configuration to install the embedded database in the X30.