FS-8700-128 Safetran SCS-128 Manual Page 12 of 15
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldSer ver.com
Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.c om
Example
// Server Side Connections
Connections
Port, Protocol, Baud, Parity, Handshaking
P8, SCS-128, 9600, None, None
5.2. Server Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for Node
Up to 32
alphanumeric
characters
Node_ID Modbus station address of physical Server Node 1-255
Protocol Specify protocol used
SCS-128
SCS128
Safetran SCS-128
Server_Hold_Timeout
Specifies t ime FieldServer will reserve Server side
connection while waiting for the C lient side to update
data in Data_Array (if necessary)
>1.0s
Example
// Server Side Nodes
Nodes
Node_Name, Node_ID , Protocol
PLC 1, 1, SCS-128
Note that no connection information is necessary on Server side