FS-8700-128 Safetran SCS-128 Manual

Page 7 of 15

4.2.Client Side Connection Descriptions

 

Section Title

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

Column Title

Function

 

Legal Values

 

 

Port

 

Specify which port the device is connected

P1-P81

 

 

 

 

 

to the FieldServer

 

 

 

 

 

 

 

 

 

 

 

SCS-128

 

 

 

Protocol

Specify protocol used

 

SCS128

 

 

 

 

 

 

 

 

Safetran SCS-128

 

 

 

Baud*

 

Specify baud rate

 

 

75, 150, 300 ,600, 1200, 2400, 9600

 

 

 

 

 

(Vendor limitation)

 

 

 

 

 

 

 

 

 

 

 

Parity*

 

Specify parity

 

 

Even (Vendor limitation)

 

 

Data_Bits*

Specify data bits

 

 

8 (Vendor limitation)

 

 

 

Stop_Bits*

Specify stop bits

 

 

1 (Vendor limitation)

 

 

 

Handshaking*

Specify hardware handshaking

 

None

 

 

 

Poll_Delay*

Time between internal polls

 

0-32000 seconds, 0.05 seconds

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

//

Client Side Connections

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

Port,

 

Protocol,

Baud,

Parity,

Handshaking,

Poll_Delay

 

 

P8,

 

SCS-128,

9600,

Even,

None,

0.100s

 

4.3.Client Side Node Descriptors

Section Title

 

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

 

Column Title

 

Function

 

 

Legal Values

 

Node_Name

Provide name for Node

 

Up

to 32 alphanumeric

 

 

characters

 

 

 

 

 

 

Node_ID

SCS-128 station address of physical Server Node

1-127

 

 

 

 

 

 

SCS-128

 

Protocol

Specify protocol used

 

 

SCS128

 

 

 

 

 

Safetran SCS-128

 

Connection

Specify which port the device is connected to the

P1-P81

 

 

FieldServer

 

 

 

 

 

 

SCS128_Ack*

If ON, Ack will be sent to Server upon receipt of every

OFF, ON

 

 

indication response

 

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

// Client Side Nodes

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

 

Node_Name,

Node_ID,

Protocol,

Connection,

 

SCS128_Ack

 

NODE_A,

1,

SCS-128,

P8,

 

 

OFF

 

1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com

Page 7
Image 7
FieldServer FS-8700-128 instruction manual Client Side Connection Descriptions, Client Side Node Descriptors