FS-8700-132 Gamewell FCI-E3 Driver Manual

Page 16 of 20

 

 

Appendix A.4. Panel Synchronization

Manual synchronization is required. When the “Reset” button on the panel is pressed a message is transmitted to the FieldServer, which clears the data in the FieldServer. After a reset the panel sends messages to report all abnormal states. When all these messages have been processed the FieldServer and panel will be synchronized. This process can be repeated at any time.

Appendix A.5. What happens when the panel sends a Reset Message

When a panel sends a reset message the driver processes every single Map Descriptor, looking at the ‘Clear on Reset’ parameter (See section 4.4.2). If the parameter is set to yes, then the driver sets all the Data Array elements referenced by the Map Descriptor to zero by looking up the Data Array Name, the Data Array offset and the length. The driver also clears the relevant sections of a Data Array specified with the DA_Bit_Name parameter.

The process can take some time. For this reason, it is suggested that you take care not to set the Map Descriptor length to a value larger than necessary.

Appendix A.5.1.

Networked Panels.

The driver can processes messages and store data from multiple panels provided that:

The panels are connected in an FCI network and the panels are configured to report their events to the main panel

The main panel is configured to send the Node of origin in a message preceding the event message. Consult with FCI for information on how to achieve this.

Example of message sent by a panel that is networked. The driver is dependent on seeing the node of event origin included in parenthesis before each event message.

Node02:

 

 

MISSING

Acclimate

L1S041 00:17:06

01/01/06

 

 

Node55: 1st Floor Lobby

 

 

DISCONNECT RSTRD

Ion Detector

L1S024 09:51:44

01/15/06

 

 

Local:

 

 

FIRST ALARM

Photo Detector

L1S001 09:24:52

12/01/06

 

 

The main panel is identified as ‘Local’. The driver interprets this as Node_ID=0.

To capture events from multiple networked panels a Node Descriptor is required for each panel with the appropriate Node_ID. Each Node requires a set of Map Descriptors.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Page 16
Image 16
FieldServer FS-8700-132, FCI E3 Series Appendix A.4. Panel Synchronization, Appendix A.5.1 Networked Panels