FS-8700-132 Gamewell FCI-E3 Driver Manual Page 7 of 20
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserv er.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldser ver.com
4.2. Client Side Connection Descriptions
Section Title
Connections
Column Title Function Legal V alues
Port Specify which port the device is connected to the FieldServer P1-P8
1
Protocol Specify protocol used FCI_E3
Baud*
Specify baud rate
Vendor documentation indicated that the only supported Baud
rate was 9600. During tes ting we learne d this was not true. The
driver was tested at 57600 and 9600 baud. Testing at 115200
Baud produced intermittent result and should not be used.
9600, 57600
(Vendor
Limitation)
Parity* Specify parity
None
(Vendor
Limitation)
Data_Bits* Specify data bits 8 (Vendor
Limitation)
Stop_Bits* Specify stop bits 1 (Vendor
Limitation)
Handshaking*
The E3 series panels do not support hand shaking.
Example
// Client Side Connections
Connections
Port, Protocol, Baud, Parity
P1, FCI_E3, 9600, None
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.