– 61 –
8-2-4. Check Code List (Outdoor)
¡ : Go on, ¥ : Flash, l : Go off
ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are two flashing LED
Remote | Sensor lamp part |
|
|
|
|
|
| Automatic | Operation | |||
controller | Block indication |
| Representative defective position |
| Detection | Explanation of error contents | ||||||
|
| reset | continuation | |||||||||
indication |
|
|
|
|
|
|
|
|
|
| ||
| Operation | Timer | Ready |
| Flash |
|
|
|
|
|
|
|
F04 | ¥ | ¥ | ¡ |
| ALT | Outdoor unit Discharge temp. sensor (TD) error |
| Outdoor | Open/Short of discharge temp. sensor was detected. | × | × | |
F06 | ¥ | ¥ | ¡ |
| ALT | Outdoor unit Temp. sensor (TE, TS, TL) error |
| Outdoor | Open/Short of heat exchanger temp. sensor was detected. | × | × | |
|
| Miswiring between TE sensor and TS sensor | ||||||||||
F08 | ¥ | ¥ | ¡ |
| ALT | Outdoor unit Outside temp. sensor (TO) error |
| Outdoor | Open/Short of outside temp. sensor was detected. | ¡ | ¡ | |
F07 | ¥ | ¥ | ¡ |
| ALT | Outdoor unit Temp. sensor (TL) error |
| Outdoor | Open/Short of heat exchanger temp. sensor was detected. | × | × | |
F12 | ¥ | ¥ | ¡ |
| ALT | Outdoor unit Temp. sensor (TS) error |
| Outdoor | Open/Short of suction temp. sensor was detected. | × | × | |
F13 | ¥ | ¥ | ¡ |
| ALT | Outdoor unit Temp. sensor (TH) error |
| Outdoor | Open/Short of heat sink temp. sensor (Board installed) was detected. | × | × | |
F15 | ¥ | ¥ | ¡ |
| ALT | Outdoor unit Misconnection of temp. sensor (TE, TS) | Outdoor | Misconnection of outdoor heat exchanger temp. sensor and suction temp. sensor was detected. | × | × | ||
F31 | ¥ | ¥ | ¡ |
| SIM | Outdoor unit EEPROM error |
| Outdoor | Outdoor P.C. board part (EEPROM) error was detected. | × | × | |
H01 | l | ¥ | l |
|
| Outdoor unit Compressor break down |
| Outdoor | When reached | × | × | |
|
|
|
| DC excitation was detected. | ||||||||
H02 | l | ¥ | l |
|
| Outdoor unit Compressor lock |
| Outdoor | Compressor lock was detected. | × | × | |
H03 | l | ¥ | l |
|
| Outdoor unit | Current detection circuit error |
| Outdoor | Current detection circuit error | × | × |
H04 | l | ¥ | l |
|
| Outdoor unit Case thermostat operation |
| Outdoor | Case thermostat operation was detected. | × | × | |
H06 | l | ¥ | l |
|
| Outdoor unit low pressure system error |
| Outdoor | Ps pressure sensor error, Low pressure protective operation | × | × | |
L10 | ¥ | ¡ | ¥ |
| SIM | Outdoor unit | Setting error of service P.C. board type | Outdoor | When outdoor service P.C. board was used, model type select jumper setting was inappropriate. | × | × | |
L29 |
|
|
|
| SIM | Outdoor unit | Other outdoor unit error |
| Outdoor | 1) Defective parts on outdoor P.C. board (MCU communication, EEPROM, TH sensor error) | × | × |
¥ | ¡ | ¥ |
|
| 2) When outdoor service P.C. board was used, model type selection was inappropriate. | |||||||
|
|
|
|
|
|
|
|
|
| 3) Other error (Heat sink abnormal overheat, gas leak, |
|
|
P03 | ¥ | l | ¥ |
| ALT | Outdoor unit | Discharge temp. error |
| Outdoor | Error was detected by discharge temp. release control. | × | × |
P04 | ¥ | l | ¥ |
| ALT | Outdoor unit |
|
| Outdoor | When case thermostat worked, error was detected by high release control from indoor/ | × | × |
| High pressure system error, Power supply voltage error | outdoor heat exchanger temp. sensor. Power supply voltage error | ||||||||||
P05 | ¥ | l | ¥ |
| ALT | Power supply error |
| Outdoor | Power supply voltage error | × | × | |
P07 | ¥ | l | ¥ |
| ALT | Outdoor unit Heat sink overheat |
| Outdoor | Abnormal overheat was detected by outdoor heat sink temp. sensor. | × | × | |
P15 | ¥ | l | ¥ |
| ALT | Gas leak detection |
| Outdoor | Abnormal overheat of discharge temp. or suction temp. was detected. | × | × | |
P20 | ¥ | l | ¥ |
| ALT | Outdoor unit | High pressure system error |
| Outdoor | Error was detected by high release control from indoor/outdoor heat exchanger temp. sensor. | × | × |
P22 | ¥ | l | ¥ |
| ALT | Outdoor unit | Outdoor fan error |
| Outdoor | Error | × | × |
P26 | ¥ | l | ¥ |
| ALT | Outdoor unit | Inverter Idc operation |
| Outdoor | × | × | |
P29 | ¥ | l | ¥ |
| ALT | Outdoor unit | Position detection error |
| Outdoor | Position detection error of compressor motor was detected. | × | × |
E01 | ¥ | l | l |
|
| No remote controller master unit |
| Remote | Signal was not received from indoor unit. | — | — | |
|
| Remote controller communication error |
| controller | Main remote controller was not set. (including 2 remote controllers) | |||||||
|
|
|
|
|
|
|
|
| ||||
E02 | ¥ | l | l |
|
| Remote controller send error |
| Remote | Signal cannot be sent to indoor unit. | — | — | |
|
|
| controller | |||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
E03 | ¥ | l | l |
|
| Regular communication error between indoor and |
| Indoor | No communication from remote controller and network adapter | ¡ | × | |
|
| remote controller |
| |||||||||
E04 | l | l | ¥ |
|
| Indoor/Outdoor serial error |
| Indoor | Serial communication error between indoor and outdoor | ¡ | × | |
E08 | ¥ | l | l |
|
| Duplicated indoor addresses | ² | Indoor | Same address as yours was detected. | ¡ |
| |
E09 | ¥ | l | l |
|
| Duplicated main remote controllers |
| Remote | In | × | × | |
|
|
| controller | (Indoor master unit stops warning and follower unit continues operation.) | ||||||||
E10 | ¥ | l | l |
|
| Communication error between CPU |
| Indoor | MCU communication error between main motor and micro computer | ¡ |
| |
E18 | ¥ | l | l |
|
| Regular communication error between master and |
| Indoor | Regular communication was impossible between master and follower indoor units. | ¡ | × | |
|
| follower indoor units |
| Communication between twin master (Main unit) and follower (sub unit) was impossible. | ||||||||
L03 | ¥ | l | ¥ |
| SIM | Duplicated indoor master units | ² | Indoor | There are multiple master units in a group. | × | × | |
L07 | ¥ | l | ¥ |
| SIM | There is group cable in individual indoor unit. | ² | Indoor | When even one group connection indoor unit exists in individual indoor unit | × | × | |
L08 | ¥ | l | ¥ |
| SIM | Unset indoor group address | ² | Indoor | Indoor address group was unset. | × | × | |
L09 | ¥ | l | ¥ |
| SIM | Unset indoor capacity |
| Indoor | Capacity of indoor unit was unset. | × | × | |
L30 | ¥ | ¡ | ¥ |
| SIM | Outside error input to indoor unit (Interlock) |
| Indoor | Abnormal stop by CN80 outside error input | × | × | |
P19 | ¥ | l | ¥ |
| ALT |
|
| Indoor | In heating operation, error was detected by temp. down of indoor heat exchanger or temp. up ofTE, TS. | ¡ | × | |
|
| Outdoor | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
²When this warning was detected before group construction/address check finish at power supply was turned on, the mode shifts automatically to AUTO address setup mode.