Digital Inverter
7 ELECTRICAL WORK
WARNING
1. | Using the specified wires, ensure that the wires are |
| connected, and fix wires securely so that the external |
| tension to the wires does not affect the connecting |
| part of the terminals. |
| Incomplete connection or fixation may cause a fire, etc. |
2. | Be sure to connect the earth wire (grounding work). |
•When the outdoor air temperature drops, power is supplied to the compressor with the purpose of preheating the compressor in order to protect it. Therefore, leave the main power switch at the “on” setting during the periods when the air conditioner is being used.
Digital Inverter
How to wire
1. | Connect the connecting wire to the terminal as identified |
| with their respective numbers on the terminal block of the |
| indoor and outdoor units. |
| H07 |
2. | When connecting the connecting wire to the outdoor unit |
| terminal, prevent water from coming into the outdoor unit. |
3. | Secure the power supply wire and indoor/outdoor |
| connecting wires using the cord clamp of the outdoor |
| unit. |
4. | For interconnecting wires, do not use a wire joined to |
| another on the way. |
Wiring diagram
*For details on the remote controller wiring/installation, refer to the Installation Manual enclosed with the remote controller.
Simultaneous twin system
Remote controller | Remote controller |
Remote controller wiring
– 105
Incomplete grounding may lead to electric shock. |
Do not connect ground wires to gas pipes, water pipes, |
lightning rods or ground wires for telephone wires. |
3. The appliance shall be installed in accordance with |
national wiring regulations. |
Capacity shortages of the power circuit or an incomplete |
installation may cause an electric shock or fire. |
CAUTION
• Wrong wiring may cause a |
parts. |
• Be sure to use the cord clamps attached to the product. |
• Do not damage or scratch the conductive core or inner |
insulator of the power and |
peeling them. |
• Use the power and |
thicknesses, specified types and protective devices |
Wiring between Indoor Unit and |
Outdoor Unit |
1.Figure below shows the wiring connections between the standard indoor and outdoor units and between the indoor units and remote controller. The wires indicated by the broken lines or dot-and-dash lines are provided at the installation place.
2.Refer to the wiring diagrams of the models concerned for the internal wiring connections of the outdoor unit and indoor units.
3.There is no need to perform the P.C. board settings for the indoor units.
Input power
380 V 3N~, 60Hz
L1 |
|
|
L2 |
| Outdoor unit |
L3 |
| |
Ν |
|
|
1 | 2 | 3 |
Use wires long enough to cover the entire length. |
5. Wiring connections differ in conformance to EMC |
standards, depending whether the system is twin, |
triple or double twin. Connect wires according to |
respective instructions. |
CAUTION
•An installation fuse must be used for the power supply line of this air conditioner.
•Incorrect/incomplete wiring may lead to an electrical fire or smoke.
•Prepare an exclusive power supply for the air conditioner.
•This product can be connected to the mains power. Fixed wire connections:
A switch that disconnects all poles and has a contact separation of at least 3 mm must be incorporated in the fixed wiring.
Indoor side
Indoor/Outdoor connecting wires
Outdoor side
A | B |
| A | B |
| |
|
|
| Indoor |
|
| |
1 | 2 | 3 | side | 2 | 3 | |
1 | ||||||
1 | 2 | 3 | Indoor power |
| ||
|
|
| ||||
L1 | L2 | L3 | N |
|
| |
|
| |||||
380 V 3N~, 60Hz |
|
|
–
required. |
• Remove the panel, and you can see electric parts on the |
Leakage breaker
1 2 3
1 2 3
1 2 3
Simultaneous triple and double twin system
front side. |
• A metal pipe can be installed through the hole for wiring. |
If the hole size does not fit the wiring pipe to be used, drill |
the hole again to an appropriate size. |
Indoor unit
(main)
A B
Indoor unit (secondary)
A B
Indoor unit
(secondary)
A B
Remote controller | Remote controller |
Remote controller wiring
Remote controller |
| Remote controller |
| ||
|
Furthermore, be sure to secure these wires with the pipe valve fixing plate and cord clamps stored in the electric parts box.
Side D (Space: 8.5 mm)
Remote controller
Indoor side
Indoor/Outdoor connecting wires
A | B |
| A | B |
|
|
|
| Indoor side |
|
|
1 | 2 | 3 | 1 | 2 | 3 |
|
|
| Indoor power |
|
|
A B
Indoor side
1 2 3
Indoor power
A B
Indoor side
1 2 3
Indoor power
Side C (Space: 4 mm)
• Secure the indoor/outdoor connecting wires at side C.
Electric parts box
Power and Wiring Specifications
Model | 224AT8 | 280AT8 | 224AT7 | 280AT7 | |
Power supply | 380 V 3N~ | ||||
50 Hz | 60 Hz | ||||
| |||||
Maximum | 18.0 A | 22.0 A | 18.0 A | 22.0 A | |
running current | |||||
|
|
|
| ||
Installation |
|
|
|
|
Outdoor side
1 | 2 | 3 | |
L1 | L2 | L3 | N |
380 V 3N~, 60Hz | |||
|
|
| Triple |
Double twin
Cord clamp
Pipe hole
Pipe valve fixing plate | Panel |
fuse rating | 25 A | 25 A | 25 A | 25 A | |
|
|
|
| ||
Power wire* |
| 5 υ 2.5 mm2 or more |
| ||
(H07 | |||||
| |||||
Indoor/outdoor |
| 4 υ 1.5 mm2 or more |
| ||
connecting | (H07 | ||||
wires* | |||||
|
|
|
|
*Number of wire υ wire size
*Use
*Connect earth wires for each indoor unit in the simultaneous twin, simultaneous triple and simultaneous double twin systems.
EN | 17 | 18 | EN |