Systematic diagram of refrigerating cycle

RAV-SM2244 series

 

 

 

Pressure

 

 

Pipe surface temperature (°C)

 

 

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

Indoor heat

Outdoor heat

 

temp. conditions

 

 

 

 

 

 

 

 

drive revolution

Indoor

 

 

(MPa)

(kg/cm²g)

Discharge

Suction

(DB/WB) (°C)

 

 

exchanger

exchanger

frequency

fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(rps)

 

 

 

 

 

Pd

Ps

Pd

Ps

(TD)

(TS)

(TC)

(TE)

 

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

3.14

0.88

32.0

9.0

84

14

10

37

64

 

HIGH

27/19

35/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Overload

3.54

1.14

36.1

11.6

88

17

16

46

62

 

HIGH

32/24

43/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

1.65

0.65

16.8

6.6

41

7

5

0

36

 

LOW

18/15.5

–15/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

2.60

0.67

26.5

6.8

73

2

42

2

66

 

HIGH

20/–

7/6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Overload

3.24

1.08

33.1

11.0

77

14

52

13

36

 

LOW

30/–

24/18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

2.05

0.31

20.9

3.2

76

–12

34

–11

75

 

HIGH

15/–

–10/(70%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This compressor has a 4-pole motor.

The value when compressor frequency (Hz) is measured by a clamp meter is twice the compressor revolution number (rps).

This data is cycle data obtained by combining a four-way ceiling cassette simultaneous twin at a target pipe length. Data will change depending on the mounted pipe length or combination with the indoor unit.

RAV-SM2804 series

 

 

 

Pressure

 

 

Pipe surface temperature (°C)

 

 

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

temp. conditions

 

 

 

 

 

 

 

 

Indoor heat

Outdoor heat

drive revolution

Indoor

 

 

(MPa)

(kg/cm²g)

Discharge

Suction

(DB/WB) (°C)

 

 

exchanger

exchanger

frequency

fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(rps)

 

 

 

 

 

Pd

Ps

Pd

Ps

(TD)

(TS)

(TC)

(TE)

 

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

3.15

0.79

32.1

8.1

87

11

9

41

80

 

HIGH

27/19

35/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Overload

3.62

1.12

36.9

11.4

89

18

16

48

64

 

HIGH

32/24

43/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

1.66

0.64

16.9

6.5

42

6

5

0

36

 

LOW

18/15.5

–15/–

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

2.85

0.63

29.1

6.4

80

1

47

2

80

 

HIGH

20/–

7/6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Overload

3.26

1.06

33.3

10.8

78

14

53

12

36

 

LOW

30/–

24/18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

2.05

0.29

20.9

3.0

81

–13

33

–12

96

 

HIGH

15/–

–10/(70%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This compressor has a 4-pole motor.

The value when compressor frequency (Hz) is measured by a clamp meter is twice the compressor revolution number (rps).

This data is cycle data obtained by combining a four-way ceiling cassette simultaneous twin at a target pipe length. Data will change depending on the mounted pipe length or combination with the indoor unit.

– 32 –

Page 32
Image 32
Toshiba RAV-SM2244AT8Z-E, RAV-SM2804AT8Z-E Systematic diagram of refrigerating cycle, RAV-SM2244 series, RAV-SM2804 series