Toshiba RAV-SM2804AT7Z Defrost control, Short interrupted operation preventive control

Models: RAV-SM2244AT8Z-E RAV-SM2804AT7ZG RAV-SM2804AT7 RAV-SM2804AT7Z RAV-SM2244AT7 RAV-SM2804AT8-E RAV-SM2244AT7Z RAV-SM2244AT7ZG RAV-SM2804AT8Z-E RAV-SM2244AT8ZG-E RAV-SM2804AT8ZG-E

1 133
Download 133 pages 47.63 Kb
Page 51
Image 51
4.Defrost control

4.Defrost control

1)During heating operations, defrost operations are performed when the temperature from the TE sensor satisfies any of the conditions in the A to D zones.

2)During defrosting operations, defrost will be terminated if the temperature from the TE sensor continues at 12°C or higher for 3 seconds or if the temperature is 7°C TE < 12°C for 1 minute.

Furthermore the defrost operation will be terminated if defrosting operations have continued for 10 minutes even if TE sensor temperature is less than 7°C.

3)After defrost operations have been reset, the compressor restarts heating operations without stopping.

Start warming operation

 

 

 

 

 

 

 

 

 

 

0

10

 

15

39

45

55

90 [min.]

TE [˚C]

 

 

 

 

 

 

 

 

 

 

 

 

 

–2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

–5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A zone

 

 

–10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D zone

 

 

 

 

 

 

 

 

B zone

 

 

 

 

 

 

 

 

 

 

 

 

–18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C zone

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The minimum TE value during 10 and 15 minutes after starting heating operation is stored as TEO.

 

When To is normal

When To is abnormal

A Zone

Status [(TEO-TE)(ToO-To)

3°C] continues for 20 seconds

Status [TEO- TE

3°C] continues for 20 seconds

B Zone

Status [(TEO-TE)(ToO-To)

2°C] continues for 20 seconds

Status [TEO-TE

2°C] continues for 20 seconds

C Zone

 

Status [TE 23°C] continues for 20 seconds

 

D Zone

When compressor operation status TE < 2°C is calculated for d minutes

 

 

 

 

 

4)The above time of d can be changed by selecting jumper [J805] or [J806]. (Setting at shipment; 90 minutes)

J805

J806

d

 

 

 

 

 

¡

¡

150 minutes

 

 

 

 

 

¡

×

90 minutes (Setting at shipment)

 

×

¡

60 minutes

 

×

×

30 minutes

¡ : Short-circuit, × : Open

 

5.Short interrupted operation preventive control

1)Even when a thermostat OFF signal is received from the indoor unit, the compressor may not stop during an 8 minute period after startup in order to protect the compressor.

This operation is not an error condition.

2)When operation is terminated by using a remote controller, operation will not continue.

6.Electrical current release control

An AC current detection value from T611 on the IPDU control board is used to suppress the revolution number of the compressor so that the input current of the inverter does not exceed a specified value.

A Zone

Normal operation.

 

Current (A)

 

 

D Zone

Maintain frequency of current operation.

B zone

 

 

 

 

B Zone

Reduce operating frequency.

l1

 

 

 

C Zone

Cease reduction of operating frequency

 

 

 

 

 

 

 

and maintain frequency of current operation.

 

 

 

 

 

 

 

D zone

C zone

 

 

 

l1–0.5

 

 

 

 

 

 

 

 

SM224 Type

SM280 Type

 

 

 

l1 value (A)

15.7

17.6

 

 

A zone

 

– 51 –

Page 51
Image 51
Toshiba RAV-SM2804AT7Z Defrost control, Short interrupted operation preventive control, Electrical current release control