– 88 –

 

SW804

 

Operation when pushdown button switch SW801 is pushed

 

 

 

 

 

 

 

 

 

 

SW804

 

 

4-way valve relay operation (For RY700, CN70 check)

 

 

 

 

 

Turn on 4-way valve power relay (RY700).

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

When pushing SW801 again or when 2 minutes elapsed,

 

 

 

 

 

 

 

 

 

1

2

3

4

 

the operation returns to the normal control.

 

 

 

 

 

 

 

 

 

 

 

SW804

 

 

SV valve relay operation (For RY702, CN702 check)

 

 

 

 

 

Turn on SV valve relay (RY702).

 

 

 

 

 

 

 

 

 

ON

 

 

 

[CAUTION]

 

 

 

 

 

When pushing SW801 again or when 2 minutes

 

 

 

 

 

 

 

 

 

 

 

 

Although these operations can

 

1

2

3

4

 

elapsed, the operation returns to the normal control.

 

 

 

 

 

 

 

be performed even during

 

 

 

 

 

 

 

operation, basically perform

 

 

 

 

 

 

Heater output relay operation

operation while the unit stops.

 

 

SW804

 

 

If performing this operation

 

 

 

 

(For check RY703, CN703 check)

 

ON

 

 

 

 

Turn on relay for option heater (RY703).

during driving the unit, it is

 

 

 

 

 

 

dangerous because the

 

 

 

 

 

 

When pushing SW801 again or when 2 minutes

 

1

2

3

4

 

pressure may change suddenly.

 

 

 

 

 

 

elapsed, the operation returns to the normal control.

 

 

 

 

 

 

 

 

 

 

 

SW804

 

 

Outside output relay operation (RY704, CN704)

 

 

 

 

 

Turn on relay for outside output (RY704).

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

When pushing SW801 again or when 2 minutes

 

 

 

 

 

 

 

 

 

1

2

3

4

 

elapsed, the operation returns to the normal control.

 

 

 

 

 

 

 

 

 

 

 

SW804

 

 

Forced start command

 

 

 

 

 

The indoor unit connected to the system is forcedly started.

 

 

 

 

 

 

 

ON

 

 

 

 

(The indoor unit starts operation by setting of the operation mode on the remote controller.)

 

 

 

 

 

 

 

1

2

3

4

 

 

 

 

 

 

 

 

 

 

 

 

 

SW804

 

 

Forced stop command

 

 

 

 

 

The indoor unit connected to the system is forcedly stopped.

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

 

 

 

 

 

 

 

 

 

 

 

 

 

SW804

 

 

Relay operation change for outside output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

[CAUTION]

 

 

 

 

 

 

 

 

 

1

2

3

4

 

Do not use this setting.

 

 

 

 

 

 

 

 

 

– 88 –

Page 88
Image 88