14. DETACHMENTS

14-1. Outdoor Unit

RAV-SM224, RAV-SM280 series

No.

Part name

 

Procedure

Remarks

 

 

 

 

 

 

1

Common

 

 

 

 

 

 

 

 

 

WARNING

 

 

procedure

 

Service panel

 

 

 

 

 

Stop operation of the air conditioner and turn off breaker switch.

CAUTION

Ensure wearing of gloves when performing any work in order to avoid injury from parts, etc.

1.Detachment

1)Remove the service panel. (Hexagonal screws Ø4 × 10, 3 pcs.)

Remove the screws and then pull service panel downward to remove.

2)Remove the power supply cable and the indoor/ outdoor connecting wire from the cord clamp and the terminal.

3)Remove the top plate.

(Hexagonal screws Ø4 × 10, 6 pcs.)

2.Attachment

1) Attach the top plate.

Top plate

(Hexagonal screws Ø4 × 10, 6 pcs.)

 

2)Connect the power supply cable and the indoor/ outdoor connecting wire to the terminal and then

fix with the cord clamp.

CAUTION

The power supply cable and the indoor/outdoor connecting wire must be affixed along the crossover pipe using a commercially available bundling band so that they do not make contact with the compressor,

gas valve, gas pipe and discharge pipe.

3)Attach the front panel.

(Hexagonal screws Ø4 ×10, 3 pcs.)

2 Discharge

1. Detachment

Setting moment

port cabinet

1)

Carry out the operation in 1. of Q above.

Upper end plate

(upper)

2)

Remove screws for the discharge port cabinet and

of heat exchanger

 

 

the inverter assembly. (ST1T Ø4 × 8, 2 pcs.)

 

 

3)

Remove screws for the discharge port cabinet and

Discharge port

 

 

the discharge cabinet.

cabinet (upper)

 

 

 

 

 

(Hexagonal screw Ø4 × 10, 2 pcs.)

 

4) Remove screw for the discharge cabinet and heat exchanger. (ST1T Ø4 × 8, 1 pc.)

5) Remove screw for the discharge port cabinet and the fin guard. (Hexagonal screw Ø4 × 10, 1 pc.)

2. Attachment

 

 

 

 

1)

Place upper left side of discharge cabinet on

 

 

 

 

 

Discharge

 

 

upper side of end board of heat exchanger and fix

 

 

 

 

port cabine

 

with a screw. (ST1T Ø4 × 8, 1 pc.)

 

 

 

 

 

 

2)

Mount other removed screws into original positions.

 

 

Heat exchanger

– 112 –

Page 112
Image 112
Toshiba RAV-SM2804AT8Z-E, RAV-SM2804AT8ZG-E, RAV-SM2244AT8ZG-E Detachments, 112, RAV-SM224, RAV-SM280 series, Attachment