13. HOW TO EXCHANGE COMPRESSOR

13-1. Exchanging Procedure of Compressor (Outline)

START

Has refrigerant recovery work been done?

YES

Turn off the leakage breaker.

Remove the defective compressor.

Mount a service compressor.

Leakage check

Vacuuming

Charge the refrigerant.

END

NO Open PMV forcedly and then recover refrigerant using a refrigerant recovery unit.

Never recover the refrigerant to the outdoor unit.

For the refrigerant recovery work during reinstallation

of repair work, be sure to use the refrigerant recovery unit.

Recovery of refrigerant to the outdoor unit is unavailable; otherwise a serious accident such as explosion or injury may be caused.

13-2. Exchange of Compressor

For exchange of compressors, refer to (11) Compressor in Section 14. Detachments.

– 111 –

Page 111
Image 111
Toshiba RAV-SM2244AT8ZG-E HOW to Exchange Compressor, Exchanging Procedure of Compressor Outline, Exchange of Compressor