Toshiba RAV-SM2244AT8Z-E, RAV-SM2804AT8ZG-E, RAV-SM2244AT8ZG-E Digital Inverter, Existing pipe SW

Models: RAV-SM2244AT8Z-E RAV-SM2804AT7ZG RAV-SM2804AT7 RAV-SM2804AT7Z RAV-SM2244AT7 RAV-SM2804AT8-E RAV-SM2244AT7Z RAV-SM2244AT7ZG RAV-SM2804AT8Z-E RAV-SM2244AT8ZG-E RAV-SM2804AT8ZG-E

1 133
Download 133 pages 47.63 Kb
Page 109
Image 109
Existing pipe SW

Digital Inverter

Are there scratches or dents on the existing pipes?

NO

Is it possible to operate the existing air conditioner?

YES

YES

NO

Existing pipes: Cannot be used.

• Use new pipes.

– 109

After the existing air conditioner is operated in cooling mode for approx. 30 minutes or longer,* recover the refrigerant.

For cleaning the pipes and recovering oil

• Refrigerant recovery: Refrigerant recovery equipment

Remove the existing air conditioner from the piping and carry out flushing (nitrogen pressure 0.5 MPa) to remove any remains inside of the pipe.

Note] In case of twin pipes, also be sure to flush the branching pipe.

Was largely discolored oil or a large quantity

of remains discharged? (When the oil

deteriorates, the color of the oil changes to a

muddy or black color.)

NO

Nitrogen gas pressure 0.5 MPa

(If there is discharge of remains, it is judged that a large quantity of remains are present.)

YES

Clean the pipes or use new pipes.

Connect the indoor/outdoor units to the existing pipe.

Use a flare nut attached to the main unit for the indoor/outdoor units. (Do not use the flare nut of the existing pipe.)

Re-machine the flare machining size to size for R410A.

When using a Ø19.1 mm pipe for the gas pipe of the first branching pipe

￿Turn the existing pipe switch on the cycle control P.C.

board of the outdoor unit to ON side. At shipment from factory OFF ￿ ON for existing pipe (Refer to the table below.) (Be sure to set the contents in the table below in order to restrict the refrigerating cycle pressure of the equipment in the pipe standard.)

Existing pipe SW

Switch

Bit 3 of SW802 ￿ ON

(Airtight test), Vacuum dry, Refrigerant charge, Gas leak check

Trial run

Piping necessary to change the flare nut/ machining size due to pipe compression

 

1) Flare nut width: H

 

 

 

(mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Copper pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

outer

Ø6.4

 

Ø9.5

Ø12.7

Ø15.9

Ø19.1

 

 

 

 

 

 

 

diameter

 

 

 

 

 

 

 

 

 

H

 

 

 

For R410A

17

 

22

26

29

36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For R22

Same as above

24

27

Same as

 

 

 

 

 

 

 

 

 

 

 

 

 

above

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2) Flare machining size: A

 

 

 

(mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

Copper pipe

Ø6.4

 

Ø9.5

Ø12.7

Ø15.9

Ø19.1

 

 

 

 

 

 

 

outer

 

 

 

 

 

 

 

 

diameter

 

 

 

 

 

 

 

 

 

 

 

 

 

For R410A

9.1

 

13.2

16.6

19.7

24.0

 

 

 

 

 

 

 

For R22

9.0

 

13.0

16.2

19.4

23.3

 

Becomes a little larger for R410A

Do not apply refrigerator oil to the flare surface.