Check

Outdoor

 

 

 

Check and troubleshooting

code

LED display

(Item without special mention Indicates part of outdoor unit.)

 

 

 

 

 

 

 

 

 

 

 

[F23]

<Display 1> <Display 2>

[PS sensor error]

 

 

 

 

 

 

 

 

¡

¡

 

 

 

 

 

 

 

 

 

 

¡

¥

Is connector of

 

NO

 

 

 

 

 

l

l

 

 

Correct connection of connector.

 

 

 

 

 

 

 

 

 

 

Ps sensor correctly connected?

 

 

 

 

 

 

l

¥

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

¡

¥

 

Connector: CN606, White

 

 

 

 

 

 

¡

¥

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are the output current characteristics

NO

 

Sensor error

 

 

 

 

 

of Ps sensor normal?

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

￿ Pressure by pressure gauge (Check joint)

 

 

 

 

 

 

￿ Pressure display on LED display

 

 

 

￿ Output power of I/F (CDB) P.C. board

 

 

 

If ￿ and ￿, ￿ and ￿ are different,

 

 

 

an error of the pressure sensor is considered.

 

 

 

If ￿ and ￿ are different, check I/F P.C. board.

 

 

 

 

 

 

 

 

 

Does not refrigerant bypass

NO

 

 

 

Check compressor.

 

from discharge port to suction port

 

 

 

 

 

 

of 4-way valve?

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check 4-way valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[F31] <Display 1> <Display 2> [EEPROM error]

¡ ¡

¡¥

l

¥

 

Check outdoor P.C. board (MCC-1599).

 

l

¥

 

 

 

Defect Replace

 

¡

¥

 

 

 

 

 

 

 

 

 

¡¥

[H01] <Display 1> <Display 2> [Compressor break down]

¡

¡

 

 

 

 

 

 

 

¡

l

Is power supply voltage normal?

 

NO

 

 

l

l

 

 

Correct power supply line.

 

 

 

AC342 to 457V

 

 

 

¡

l

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

l

l

 

 

 

 

 

 

l

¥

 

 

 

 

 

 

 

Is wire connection normal?

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor lead

 

 

Check wire connection

 

 

(Board side, Compressor side),

 

 

 

and correct it.

 

 

Reactor lead, Power supply lead

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

Is it not abnormal overload?

 

 

Correct and clear the cause.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check outdoor P.C. board (MCC-1596).

 

 

 

 

 

 

 

 

Defect Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 70 –

Page 70
Image 70
Toshiba RAV-SM2244AT7Z, RAV-SM2804AT7Z F31 Display 1 Display 2 Eeprom error, H01 Display 1 Display 2 Compressor break down