8-2-3. Monitor Function of Remote Controller Switch

nCalling of sensor temperature display

<Contents>

Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitor mode from the remote controller.

<Procedure>

1

TEST

CL

Push

+ buttons simultaneously for 4 seconds to

call the service monitor mode.

The service monitor goes on, the master indoor unit No. is displayed at first and then the temperature of item code ￿￿ is displayed.

 

ò

 

2 Push temperature set

TEMP.

buttons and then change

 

the item code of data to be monitored.

The item code list is shown below.

TEMP.

 

 

ON / OFF

 

 

TIMER SET

FAN

 

MODE

 

 

TIME

SA

 

VENT

FIL

SET CL

SWING/FIX

UNIT LOUVER

RESET TEST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

4

1

3

<Operation procedure>

 

 

Item code

Data name

Unit

 

 

 

 

 

 

 

01

Room temperature

°C

 

 

 

(Remote controller)

 

data

 

02

Indoor suction temperature (TA)

°C

 

03

Indoor heat exchanger (Coil)

°C

 

 

temperature (TCJ)

 

unit

 

 

 

 

04

Indoor heat exchanger (Coil)

°C

Indoor

 

 

 

temperature (TC)

 

07

Indoor fan revolution frequency

rpm

F2

Indoor fan calculated operation time

×100h

 

 

 

F3

Filter sign time

×1h

 

F8

Indoor discharge temperature*1

°C

 

 

 

 

 

 

 

 

1

 

2

 

 

3

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Returned to usual display

 

 

 

 

 

 

 

 

Item code

 

Data name

 

 

Unit

 

 

 

 

 

 

 

60

Outdoor heat exchanger (Coil) temperature (TE)

°C

data

 

61

Outside temperature (TO)

 

 

 

 

 

 

°C

 

62

Compressor discharge temperature (TD)

 

 

°C

 

 

 

 

unit

 

63

Compressor suction temperature (TS)

 

 

°C

 

65

Heat sink temperature (THS)

 

 

 

 

 

 

°C

Outdoor

 

6A

Operation current (× 1/10)

 

 

 

 

 

 

A

6D

Outdoor heat exchanger (Coil) temperature (TL)

°C

70

Compressor operation frequency

 

 

rps

 

72

Outdoor fan revolution frequency (Lower)

 

 

rpm

 

73

Outdoor fan revolution frequency (Upper)

 

 

rpm

 

 

F1

Compressor calculated operation time

 

 

×100h

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The item codes with marks in the above table are displayed only on the indoor units of 4 series models and after.

(4 series indoor units mean RAV-SM1404UT-E for example.).

 

ò

3

Push UNIT LOUVER button to select the indoor unit to be monitored.

 

Each data of the indoor unit and its outdoor units can be monitored.

 

ò

4

TEST

Pushing button returns the status to the usual display.

1 The indoor discharge temperature of item code [F8] is the estimated value from TC or TCJ sensor.

Use this value to check discharge temperature at test run.

(A discharge temperature sensor is not provided to this model.)

• The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.

– 60 –

Page 60
Image 60
Toshiba RAV-SM2804AT8-E, RAV-SM2804AT8ZG-E, RAV-SM2244AT8ZG-E, RAV-SM2804AT8Z-E Monitor Function of Remote Controller Switch