– 97 –

Digital Inverter

11. INSTALLATION MANUAL

Please read this Installation Manual carefully before installing the Air Conditioner.

This Manual describes the installation method of the outdoor unit.

For installation of the indoor unit, follow the Installation Manual attached to the indoor unit.

ADOPTION OF NEW REFRIGERANT

This Air Conditioner is a new type that has adopted a new refrigerant HFC (R410A) instead of the conven- tional refrigerant R22 in order to prevent destruction of the ozone layer.

This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (1) at the interface point between the user’s supply and the public system.

It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc (1).

Ssc (1)

 

 

Model

 

Ssc (MVA)

 

 

 

 

 

 

 

 

 

 

 

RAV-SM2244AT8(Z)(ZG)-E

 

1.41

 

 

 

 

 

 

 

 

 

 

 

RAV-SM2804AT8(Z)(ZG)-E

 

1.72

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Contents

 

 

 

1

ACCESSORY PARTS

 

2

2

SAFETY PRECAUTIONS

 

3

3

INSTALLATION OF NEW REFRIGERANT AIR CONDITIONER

................................ 4

4

INSTALLATION CONDITIONS

6

5

REFRIGERANT PIPING

 

10

6

AIR PURGING

 

14

7

ELECTRICAL WORK

 

17

8

EARTHING

 

19

9

FINISHING

 

20

10

TEST RUN

 

20

11

ANNUAL MAINTENANCE

 

20

12

AIR CONDITIONER OPERATING CONDITIONS

20

13

FUNCTIONS TO BE IMPLEMENTED LOCALLY

21

14

TROUBLESHOOTING

 

22

15

APPENDIX

 

24

Digital Inverter

1 ACCESSORY PARTS

„ Accessory Parts

Part name

Q’ty

Shape

Usage

Installation manual

1

 

(Hand this directly to the customer.)

Drain nipple

1

 

 

Waterproof rubber cap

1

 

 

Protective bush

1

 

For protecting wires (pipe cover)

Guard material for passage part

1

 

For protecting passage part (pipe cover)

Clamp filter

1

 

For conforming to EMC standards

 

(Used for power wire)

 

 

 

Ø19.1 mm pipe

1

 

For the pipe inside the outdoor unit

Joint (Ø19.1 – Ø25.4 mm)

1

 

For connecting the pipe

Joint (Ø25.4 – Ø28.6 mm)

1

 

For connecting the pipe

Elbow

1

 

For connecting the pipe

INFORMATION

The main pipe on the gas side of this outdoor unit has a diameter of Ø28.6 mm, but a Ø19.1 mm flare connection is used where the valve is connected. Be sure to use the Ø19.1 mm pipe and joint provided as accessories for the pipe connection.

Before installing the unit, check that the unit has the correct model name to prevent the wrong unit from being installed in the wrong place.

Before proceeding to weld the refrigerant pipe, be sure to pass nitrogen through the pipe.

Before installing the indoor units, read the instructions in the installation manual provided with the indoor units.

Before installing a branch pipe, read the instructions in the installation manual provided with the branch pipe kit.

In the case of a simultaneous double twin system, use indoor unit with the same capacity for all four indoor units.

 

Branch pipe kit

Combination indoor unit

RAV-SM2244

RBC-DTWP101E

SM56 υ 4 units

RAV-SM2804

RBC-DTWP101E

SM80 υ 4 units

P.C. board settings are required for some of the indoor units if they are to be used in a twin, triple or double twin system. Refer to the instructions in the installation manual of the branch pipe kit, and ensure that the settings are selected correctly.

Combination with the indoor units

Combination with the indoor units is possible only when units with the same type are combined. Combinations of units with different types cannot be used.