10-4. Address Setup (Manual setting from remote controller)

In case that addresses of the indoor units will be determined prior to piping work after cabling work

Set an indoor unit per a remote controller.

Turn on power supply.

(Example of 2-lines cabling)

(Real line: Cabling, Broken line: Refrigerant pipe)

Outdoor

Outdoor

1

2

3

1

2

3

1 2 3

Indoor

A B

Line address 1 Indoor unit address 1 Group address 1

1 2 3

Indoor

A B

1

2

2

1 2 3

Indoor

A B

2

1

2

1 2 3

Indoor

A B

2

2

2

1

 

 

 

 

 

 

A B

 

 

Push SET + CL + TEST

buttons simultaneously

Remote controller

 

 

 

for 4 seconds or more.

 

 

For the above example, perform setting by

2

 

 

 

 

 

 

(

Line address)

 

 

 

connecting singly the wired remote controller

 

/

buttons,

without remote controller inter-unit cable.

 

Using the temperature setup

Group address

 

 

set 12 to the CODE No.

 

 

Individual

: 0000

 

 

 

 

Master unit : 0001

In case of group control

3

 

 

 

 

 

 

 

 

 

 

 

 

Sub unit

: 0002

Using timer time

/ buttons, set the line address.

 

 

 

 

4

Push SET button. (OK when display goes on.)

 

 

 

5

(

Indoor unit address)

/

buttons, set 13

to the CODE No.

 

 

Using the temperature setup

 

6

Using timer time

/ buttons, set 1 to the line address.

 

 

7

Push SET button. (OK when display goes on.)

 

 

 

8

(

Group address)

/

buttons, set 14

to the CODE No.

 

 

Using the temperature setup

 

9

Using timer time

/ buttons, set 0000 to Individual, 0001 to Master unit, and 0002 to sub unit.

10 Push SET

button. (OK when display goes on.)

 

 

 

11 Push TEST

button.

 

 

 

 

 

 

Setup completes. (The status returns to the usual stop status.)

TEMP.

ON / OFF

2, 5, 8

END 11

1

<Operation procedure>

FILTER RESET TEST

TIMER SET

FAN

MODE

TIME

SAVE

VENT

SET CL

SWING/FIX

UNIT LOUVER

3, 6, 9 4, 7, 10

1 2 3 4 5 6 7 8 9 10 11 END

– 94 –

Page 94
Image 94
Toshiba RAV-SM2244AT7, RAV-SM2804AT8ZG-E, RAV-SM2244AT8ZG-E Address Setup Manual setting from remote controller