3.Outdoor fan revolution number control

3.Outdoor fan revolution number control

Control of fan revolution number and the fan taps in this unit are shown below.

Fan Taps Revolution number Allocation [rpm]

 

 

W1

W2

W3

W4

W5

W6

W7

W8

W9

WA

WB

WC

WD

WE

WF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM224

Upper Fan

250

280

280

310

340

400

460

520

580

640

710

760

830

860

920

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lower Fan

0

0

250

270

300

350

410

470

530

590

640

710

770

810

850

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SM280

Upper Fan

250

280

280

340

400

460

520

580

640

710

760

830

860

920

940

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lower Fan

0

0

250

300

350

410

470

530

590

640

710

770

810

850

920

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-1. Cooling fan control

1)Cooling operations of the outdoor fan are controlled by a TL sensor, TO sensor and the compressor revolution number. Control is performed per 1 tap of DC fan control.

The outdoor fan is controlled by every 1 tap of DC fan control (14 taps).

During startup, operation is fixed for 60 seconds to a maximum fan tap corresponding to the zones shown in the table below. Thereafter fan tap is controlled by a temperature outputted from the TL sensor.

 

 

Less than 45 rps

45 rps or more

60 rps or more

TL (˚C)

 

 

 

 

and less than 60 rps

 

 

 

 

 

 

 

 

58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min.

Max.

Min.

Max.

Min.

Max.

 

WF tap

 

 

 

 

 

 

 

 

 

55

 

 

38°C TO

W6

WE

W8

WF

WA

WF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

29°C TO < 38°C

W5

WD

W7

WF

W9

WF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15 TO < 29°C

W3

WA

W5

WC

W7

WE

 

(

+1 tap / 20 sec.

)

 

 

 

 

 

 

 

 

 

Until Maximum rps

5

TO < 15°C

W2

W8

W4

WA

W6

WC

 

 

in each zone

 

 

 

 

 

 

 

 

 

 

 

 

0

TO < 5°C

W1

W6

W3

W8

W4

WA

 

 

 

 

 

 

 

 

 

 

 

 

37

 

 

 

–5 TO < 0°C

W1

W5

W2

W7

W3

W8

Revolution number HOLD

34

TO < –5°C

W1

W4

W3

W5

W3

W6

 

 

 

(

–1 tap / 20 sec.

)

 

TO error

W1

WE

W3

WF

W3

WF

 

Until Minimum rps

 

in each zone

3-2 Heating fan control

1)Heating operations of the outdoor fan are controlled by a TE sensor, TO sensor and the compressor revolution number.

(Control from a minimum W1 to a maximum is performed according to the table below).

2)Operation is fixed for 3 minutes after start up by a maximum fan tap corresponding to the zones in the table below. Thereafter fan control is performed using the temperature from the TE sensor.

3)When TE 24°C continues for 5 minutes, the compressor is stopped. The compressor is placed in the same state as a normal thermostat OFF without an error display.

The compressor is restarted after approximately 2 minutes 30 seconds and such interrupted operation does not constitute an error. When the operation in 3) above is frequently performed, the filter of the intake section of the indoor unit may require cleaning.

Therefore restart operation after cleaning the filter.

 

 

 

Less than

45 rps or more

60 rps

 

 

 

45 rps

and less than 60 rps

or more

 

 

 

 

 

 

10°C TO

WA

WB

WC

 

 

 

 

 

 

5 TO < 10°C

WC

WD

WF

 

 

 

 

 

 

Maximum

–3

TO < 5°C

WF

WF

WF

 

 

 

 

 

–10

TO < –3°C

WF

WF

WF

 

 

 

 

 

 

 

TO < –10°C

WF

WF

WF

 

 

 

 

 

 

TO error

WF

WF

WF

 

 

 

 

 

 

TE (˚C)

–2 taps / 20 sec. Stop timer count (Until W1)

24

–2 taps / 20 sec.

(Until W1)

21

–1 tap / 20 sec.

(Until W1)

18

Revolution number HOLD

15

+1 tap / 20 sec.

– 50 –