12.SV2 valve control

The conditions for opening and closing the SV2 valve are shown in the table below.

 

 

 

SV2 Valve “Open” Conditions

SV2 Valve “Close” Conditions

 

 

 

 

 

 

 

(1)

When operation stopped after operating

When operation started after operating or when 30 minutes

Non-operation

 

 

(2)

When power placed “ON”

elapsed after opening SV2 under conditions (1) (2)

 

 

 

 

 

 

 

 

 

 

During Cooling

(3)

When 30 second elapses after first startup

When 8 minutes elapsed after starting operation.

operation when power ON at TO 5° C

 

 

 

Operations

 

 

 

(4)

When Ps 0.23 MPa

When Ps 0.27 MPa

 

 

 

 

 

 

 

During Heating

(5)

When 30 second elapses after first startup

When 8 minutes elapsed after starting operation or when

operation when power ON at TC < 26°C

TC 26°C

 

Operations

 

 

 

(6)

When Ps 0.14 MPa

When Ps 0.19 MPa

 

 

 

 

 

 

 

 

During

(7)

When conditions for defrost satisfied.

When 4-way valve is OFF during defrost startup.

 

Defrost

 

 

When 2 minutes elapsed after four-way valve is ON after

 

Operation

(8)

When conditions for defrost satisfied.

 

defrost completion

 

 

 

 

 

 

 

 

 

Defrost

Defrost

start condition

completion condition

Defrost operation

66rps

Compressor revolution number

36rps

4-way valve

ON

OFF

 

 

2 minutes

SV2

Open

Close

 

13.Oil recovery control

1)This control enables periodic recovery of oil accumulating in the indoor unit or in the exchange pipe.

2)After continuous operation for 240 minutes, the lower limit for the compressor revolution number is raised for 2 minutes and oil is recovered.

 

Control Conditions

Control Details

 

 

 

During Cooling

Continuous cooling operation for 240 minutes

Lower limit for compressor revolution number placed to 56 rps per

2 minutes

 

 

 

 

 

During Heating

Continuous heating operation for 240 minutes

Lower limit for compressor revolution number placed to 70 rps per

2 minutes

 

 

 

 

 

3)

 

When low

The compressor rotation speed is raised to the lower limit

During startup of oil recovery control, the compressor

during control.

 

 

 

revolution number during operation is lower than the

 

Operate according to indoor commands without lowering

revolution number of the lower limit for control details.

 

When high

the compressor rotation speed to the lower limit.

 

 

(In this case, the timer counts 2 minutes.)

 

 

 

4)When the DOWN zone and the HOLD zone (UP prohibition) are superimposed for example during current release control or discharge temperature release control, DOWN zone and the HOLD zone have priority over oil recovery control.