Check

Outdoor

 

 

 

Check and troubleshooting

 

code

LED display

(Item without special mention Indicates part of outdoor unit.)

 

 

 

 

 

[H06]

<Display 1>

<Display 2> [Low pressure protective operation]

 

 

¡

¡

 

 

 

 

 

 

 

 

 

 

 

 

¡

l

Are gas pipe, liquid pipe

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

l

l

and service valve of the

 

 

 

 

 

Open the service valve fully.

 

 

 

 

 

 

 

 

 

 

 

outdoor unit fully opened?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

¡

¥

YES

 

 

 

 

 

 

 

 

 

 

l

 

 

 

 

 

 

 

 

 

 

 

¥

Are the pressure

 

 

 

NO

 

 

 

 

 

l

l

sensor characteristics of

 

 

 

 

 

Replace low pressure sensor.

 

 

 

 

 

 

 

 

 

 

 

 

 

low pressure normal?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

￿ Pressure by pressure gauge (Check joint)

 

 

 

 

 

 

 

￿ Pressure indication by LED

 

 

 

 

 

 

 

￿ Output power of I/F (CDB) P.C. board

 

 

 

 

 

 

 

 

If ￿ and ￿, ￿ and ￿ are different,

 

 

 

 

 

 

 

 

an error of the pressure sensor is considered.

 

 

 

 

 

 

 

 

If ￿ and ￿ are different, check P.C. board.

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

Is SV2 circuit normal?

 

 

Correct SV2 circuit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

Check miss-wiring, wrong installation and connection of connector.

 

 

 

 

Isn’t any indoor unit

 

 

 

YES

 

 

 

 

 

 

 

which has different refrigerant

 

 

 

 

Correct wiring to regular wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

system connected?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

(Using miss-wiring check function of the outdoor unit, check them.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In cooling season, go to A .

In heating season, go to B .

ACooling

 

 

 

 

 

 

NO

 

 

 

Are parts related to the

 

 

NO

 

 

 

 

 

 

Does cooling

 

 

 

 

indoor fan motor normal?

 

 

 

 

Repair the

 

 

 

 

 

 

 

 

 

1. Connection of connector

 

 

 

 

 

 

indoor fan normally operate?

 

 

 

 

 

 

 

 

 

 

 

 

defective position.

 

 

 

 

 

 

 

 

2. Capacitor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

YES

 

 

 

3. Motor 4. Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there clogging of indoor filter

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cleaning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or heat exchanger?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check indoor P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defective

Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant shortage, clogging

 

 

 

 

 

 

 

Are connection of connectors

 

 

 

 

Repair the

 

or pipe breakage is considered.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and coils normal?

 

 

 

 

 

defective position.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is blocking found in entire valve?

 

 

 

Replace PMV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

with new one.

 

 

B Heating

 

 

NO

 

 

 

Is indoor fan

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Does heating outdoor fan

 

 

 

 

system normal?

 

 

 

 

 

Repair the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

normally operate?

 

 

 

 

 

 

 

·Fan breakage

 

 

 

 

 

 

 

defective position.

 

 

YES

 

 

 

YES

 

 

 

·Fan coming-off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there clogging of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cleaning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outdoor heat exchanger?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check outdoor P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

Defective

Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is outdoor PMV normal?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shortage of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

refrigerant/blocking/pipe breakage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[L10] <Display 1>

<Display 2>

[Unset model type]: Only when service P.C. board is used

¡

¡

 

 

 

 

 

¡

l

 

 

 

 

 

l

¥

 

 

Cut jumper line according

 

 

¡

l

 

 

to the explanation sheet packaged

 

 

 

 

with the service P.C. board.

 

 

¡

¥

 

 

 

 

 

 

 

 

 

 

 

 

 

l

l

 

 

 

 

 

 

 

 

 

 

 

 