Toshiba RAV-SM2804AT7Z, RAV-SM2804AT8ZG-E, RAV-SM2244AT8ZG-E 117, Detachment, Attachment

Models: RAV-SM2244AT8Z-E RAV-SM2804AT7ZG RAV-SM2804AT7 RAV-SM2804AT7Z RAV-SM2244AT7 RAV-SM2804AT8-E RAV-SM2244AT7Z RAV-SM2244AT7ZG RAV-SM2804AT8Z-E RAV-SM2244AT8ZG-E RAV-SM2804AT8ZG-E

1 133
Download 133 pages 47.63 Kb
Page 117
Image 117
– 117 –

No. Part name

Procedure

Remarks

7 Fan-IPDU

1. Detachment

FAN-IPDU board

board

1) Carry out the operation in 1. of Q, 1. of R and

 

MCC-1597

1. of T above.

 

2)Remove lead wires and connectors to other components from the Fan-IPDU board.

CN700 : Relay connector (3P, Blue)

CN750 : Outdoor fan motor (3P, White)

CN500 : Connection between reactor and noise filter board (7P, Red)

CN502 : Compressor IPDU board (3P, White)

CN602 : Noise filter board (2P, White)

CN504 : Interface board (5P, Blue)

CN505 : Compressor IPDU board (5P, Red)

Connectors should be removed after unlocking the housing section.

3)Remove screw fixing the earth wire.

4)Remove the claw of the support (3 positions) fixing the board and the screw (5 positions) fixing the

heat sink and then remove the Fan-IPDU board.

Earth wire

2. Attachment

1)Mount Fan-IPDU board

2)Mount components in the opposite method to that when removing.

Screw (5 positions)

Screw

Support (3 positions)

Heat sink

State of Fan-IPDU board when removed

– 117 –