– 108 –
Digital Inverter
No. | Cause |
| Display mode 1 |
|
| Display mode 2 |
| |||||
D800 | D801 | D802 | D803 | D804 | D800 | D801 | D802 | D803 | D804 | |||
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
| ||
1 | Normal |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| ||
2 | Discharge (TD) sensor error |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| ||
3 | Heat exchanger (TE) sensor error |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| ||
4 | Heat exchanger (TL) sensor error |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| ||
5 | Outside air temperature (TO) sensor error |
|
|
|
|
|
|
|
|
|
6 Suction (TS) sensor error
7 Heat sink (TH) sensor error
8 Outdoor temperature sensor (TE/TS) connection error
9 Outdoor EEPROM error
10 Compressor lock
11 Compressor lock
12 Current detection circuit error
13 Thermostat for compressor activated
14 Model data not set (on the service P.C. board)
15
16 Discharge temperature error
17 Abnormal power (open phase detected or abnormal voltage)
18 Heat sink overheat
19 Gas leak detected
20
21 High pressure release operation
22 Outdoor fan motor error
23 Compressor driver
24 Position detection circuit error in
25 Ps sensor error
26 Ps drop down error
(: OFF : ON : Flashing)
*The LEDs and DIP switches are
located on the lower left of the P.C. | ON |
| ON | ||||||||||||||||
board of the outdoor unit. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 | 2 | 3 | 4 | 1 | 2 | 3 | 4 |
| |
SW804 |
| SW805 | Enlarged view of | ||||||
|
|
|
|
| ON |
|
|
| LEDs |
ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| D805 |
| 1 |
| 2 |
| 3 |
| 4 |
|
| 1 |
| 2 |
| 3 |
| 4 |
|
|
|
|
|
|
|
|
| SW802 | SW803 | SW800 SW801 SW806 |
|
|
| D804 | |||||||||||||||||
|
|
|
| |||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| LED |
|
|
| D803 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| D802 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| D805 |
|
|
| D801 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| D804 |
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| D803 |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| D800 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| D802 |
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| D801 |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| D800 |
|
|
|
|
|
Digital Inverter
15 APPENDIX
Work instructions
The existing R22 and R407C piping can be reused for our digital inverter R410A product installations.
WARNING
Confirming the existence of scratches or dents on the existing pipes and confirming the reliability of the pipe strength are conventionally referred to the local site.
Basic conditions needed to reuse existing pipes
Check and observe the presence of three conditions in the refrigerant piping works.
1.Dry (There is no moisture inside of the pipes.)
2.Clean (There is no dust inside of the pipes.)
3.Tight (There are no refrigerant leaks.)
Restrictions for use of existing pipes
In the following cases, the existing pipes should not be reused as they are. Clean the existing pipes or exchange them with new pipes.
1.When a scratch or dent is heavy, be sure to use new pipes for the refrigerant piping works.
2.When the existing pipe thickness is thinner than the specified “Pipe diameter and thickness,” be sure to use new pipes for the refrigerant piping works.
•The operating pressure of R410A is high (1.6 times that of R22 and R407C). If there is a scratch or dent on the pipe or a thinner pipe is used, the pressure strength may be inadequate, which may cause the pipe to break in the worst case.
*Pipe diameter and thickness (mm)
Reference outside | Wall thickness | Material | |
diameter (mm) | (mm) | ||
| |||
6.4 | 0.8 | — | |
9.5 | 0.8 | — | |
12.7 | 0.8 | — | |
15.9 | 1.0 | — | |
19.1 | 1.2 | — | |
|
|
| |
22.2 | 1.0 | Half hard | |
|
|
| |
28.6 | 1.0 | Half hard | |
|
|
|
3.When the outdoor unit was left with the pipes disconnected, or the gas leaked from the pipes and the pipes were not repaired and refilled.
•There is the possibility of rain water or air, including moisture, entering the pipe.
4.When refrigerant cannot be recovered
•There is the possibility that a large quantity of dirty oil or moisture remains inside the pipes.
5.When a commercially available dryer is attached to the existing pipes
•There is the possibility that copper green rust has been generated.
6.When the existing air conditioner is removed after refrigerant has been recovered.
Check if the oil is judged to be clearly different from normal oil.
•The refrigerator oil is copper rust green in color: There is the possibility that moisture has mixed with the oil and rust has been generated inside the pipe.
•There is discolored oil, a large quantity of residue, or a bad smell.
•A large quantity of shiny metal dust or other wear residue can be seen in the refrigerant oil.
7.When the air conditioner has a history of the compressor failing and being replaced.
•When discolored oil, a large quantity of residue, shiny metal dust, or other wear residue or mixture of foreign matter is observed, trouble will occur.
8.When temporary installation and removal of the air conditioner are repeated such as when leased etc.
9.If the type of refrigerator oil of the existing air conditioner is other than the following oil (Mineral oil), Suniso, Freol- S, MS (Synthetic oil), alkyl benzene (HAB,
•The
NOTE
The above descriptions are results have been confirmed by our company and represent our views on our air conditioners, but do not guarantee the use of the existing pipes of air conditioners that have adopted R410A in other companies.
Branching pipe for simultaneous operation system
•In the concurrent twin system, when TOSHIBA has specified that branching pipe is to be used, it can be reused.
Branching pipe model name:
RBC-TWP30E2, RBC-TWP50E2, RBC-TRP100E
On the existing air conditioner for simultaneous operation system (twin, triple, double twin system), there are cases of branch pipes being used that have insufficient compressive strength.
In such case, please change the piping to a branch pipe for R410A.
Curing of pipes
When removing and opening the indoor or outdoor unit for a long time, cure the pipes as follows:
•Otherwise rust may be generated when moisture or foreign matter due to condensation enters the pipes.
•The rust cannot be removed by cleaning, and new pipes are necessary.
Placement location | Term | Curing manner | |
Outdoors | 1 month or more | Pinching | |
Less than 1 month | Pinching or taping | ||
| |||
Indoors | Every time | ||
|
EN | 23 | 24 | EN |