Digital Inverter

13 FUNCTIONS TO BE IMPLEMENTED LOCALLY

Digital Inverter

14 TROUBLESHOOTING

„Handling Existing Pipe

When using the existing pipe, carefully check for the following:

Wall thickness (within the specified range)

Scratches and dents

Water, oil, dirt, or dust in the pipe

Flare looseness and leakage from welds

Deterioration of copper pipe and heat insulator

Before recovering the refrigerant in the existing system, perform a cooling operation for at least 30 minutes.

Cautions for using existing pipe

When using a Ø19.1 mm gas pipe for the existing piping, set bit 3 of SW802 (switch for existing pipe) on the P.C. board of the outdoor unit to ON. In this case, the heating performance may be reduced depending on the outside air temperature and room temperature.

SW802

When shipped from factory

When using existing pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

4

 

 

 

 

 

3

 

 

 

 

 

3

 

 

ON

 

 

2

 

 

ON

 

 

2

 

 

 

 

1

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition to using the check codes displayed on the wired remote controller of the indoor unit.

Use the LEDs and check codes for various checks. Details of the check codes displayed on the wired remote controller of the indoor unit are described in the Installation Manual of the indoor unit.

Verifying current abnormal status

1.Check that DIP switch SW803 is set to OFF.

2.Jot down the states of LED800 to LED804. (Display mode 1)

3.Press SW800 for at least 1 second. The LED status changes to display mode 2.

4.Check the code whose display mode 1 equals the LED states jotted down and display mode 2 equals the current flashing status of LED800 to LED804 from the following table to identify the cause.

– 107 –

Do not reuse a flare nut to prevent gas leaks.

Replace it with the supplied flare nut and then process it to a flare.

Blow nitrogen gas or use an appropriate means to keep the inside of the pipe clean. If discolored oil or much residue is discharged, wash the pipe.

Check welds, if any, on the pipe for gas leaks.

There may be a problem with the pressure resistance of the branching pipes of the existing piping. Replace them with branch pipes (sold separately).

When the pipe corresponds to any of the following, do not use it. Install a new pipe instead.

The pipe has been opened (disconnected from indoor unit or outdoor unit) for a long period.

The pipe has been connected to an outdoor unit that does not use refrigerant R22, R410A or R407C.

The existing pipe must have a wall thickness equal to or larger than the following thicknesses.

Reference outside

Wall thickness

Material

diameter (mm)

(mm)

 

6.4

0.8

9.5

0.8

12.7

0.8

15.9

1.0

19.1

1.2

22.2

1.0

Half hard

 

 

 

28.6

1.0

Half hard

 

 

 

Do not use any pipe with a wall thickness less than these thicknesses due to insufficient pressure capacity.

„Recovering Refrigerant

Use the refrigerant recovery equipment to recover the refrigerant.

Verifying an abnormal state in the past although the abnormal state no longer occurs

1.Set bit 1 of DIP switch SW803 to ON.

2.Jot down the states of LED800 to LED804. (Display mode 1)

3.Press SW800 for at least 1 second. The LED status changes to display mode 2.

4.Find an error whose display mode 1 equals the LED states jotted down and display mode 2 equals the current flashing states of LED800 to LED804 from the following table to identify the error.

• An outside air temperature (TO) sensor error can be checked only while it occurs.

EN

21

22

EN

Page 107
Image 107
Toshiba RAV-SM2804AT7, RAV-SM2804AT8ZG-E, RAV-SM2244AT7ZG 107, SW802, Reference outside Wall thickness Material Diameter mm