9-3. Outdoor Unit

9-3. Outdoor Unit

9-3-1. Various Setting on Outdoor Unit (Existing piping, Power save, Cooling-only, etc.)

The following settings are available by DIP switch setup and jumper line setup.

Function

 

 

 

 

 

 

 

 

 

 

Set position

 

 

 

Control contents

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Existing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn the switch to ON when Ø19.1 is used for the existing pipe.

piping setup

 

 

 

 

SW802

In this case, the heating capacity may lower according to outside

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

temp. and indoor temp. in heating operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power save

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn the switch to ON when using the power save function.

setup

 

1

 

2 3 4

 

 

 

The control to lower the compressor frequency (Approx. –10%) is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

performed by indoor heat exchanger temp. in heating operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Existing piping setup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When snow enters from clearance of the fan guard or heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power save setup

 

 

 

 

 

 

 

 

 

 

 

 

 

Snow-proof

 

 

 

 

 

 

 

 

 

 

Snow-proof fan control

exchanger into blast path and it is accumulated, the control to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

all are OFF at shipment.

prevent generation of motor lock is validated.

 

 

 

fan control

 

 

 

 

 

When outside temp. is below 0°C though the compressor stops,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the outdoor fan operates with W5.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost

 

 

 

 

 

 

 

 

 

 

J805, J806

The defrost interval is cut to shorten it than the standard status.

 

 

 

 

 

 

 

 

 

 

For contents of control and cutting method, refer to Section

time change

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7-4. Defrost control.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When it is needed to lower the maximum value of the compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

frequency, cut the jumper line. Max. frequency at cooling/heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is lowered.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In this case the Max. capacity decreases.

 

 

 

Max. frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. frequency of compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J807

 

 

 

 

 

 

 

 

 

 

change

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RAV-SM224

 

RAV-SM280

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL

 

HEAT

 

COOL

HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard status

 

78.0

 

74.4

 

91.2

96.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When J807 is cut

 

66.6

 

66.6

 

76.8

76.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling-only

 

 

 

 

 

 

 

 

 

 

 

 

 

J808

When using the air conditioner as a cooling-only conditioner, cut

 

 

 

 

 

 

 

 

 

 

 

 

 

the jumper line. (An air conditioner can be changed to cooling-only

setup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

conditioner by “0F” of DN code on the remote controller.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 