(3)Outdoor unit does not run.

4. Service procedures

(3)Outdoor unit does not run.

A. Check COOL/FAN selector switch in the remote control unit.

• Is COOL/FAN selector switch

NO

 

 

 

Set to COOL.

set to COOL ?

 

 

 

 

 

 

 

 

 

0623_X_S

B.Check set temperature.

Try to lower set

temperature by Temperature setting button “COOLER”.

B.Check set temperature. YES

Set “Operation selector” switch to TEST in the indoor unit.

C.Outdoor unit is abnormal. Outdoor unit runs.

Is room temperature too low ?

a)Check power supply wiring NO

Try to run both indoor and outdoor units with another remote control unit.

Manual background OK

The other remote control unit is defective.

(Room sensor in the remote control unit is defective.)

0624_X_S

C.Outdoor unit is abnormal.

a)Check power supply wiring

Check negative phase relay. (47C)

Dose it operate ?

Manual background NO

Rewire power supply cords.

0625_X_S