4-1 Trobleshooting

4. Service procedures

4

4-1 Trobleshooting

(1) Check before and after Troubleshooting

Many problems may happen because of wiring or power supply problems, so you should check these areas first. Problems here can cause false results in some of the other tests, and so should be corrected first.

1. Check power supply wiring

(a)Single-phase

Check that power supply wires are correctly connected to terminal No. 1 through No. 4 on the 4P terminal plate in the indoor unit and L and N on the 6P terminal in the outdoor unit.

(b)3-phase

Check that power supply wires are correctly connected to terminal No. 1 through No. 4 on the 4P terminal plate in the indoor unit and L1 through L3 and N on the 8P terminal in the outdoor unit.

2. Check inter-unit wiring

Check that inter-unit control wiring (AC 220 - 240 V Line voltage) is correctly connected between the indoor unit and outdoor unit.

Single-phase outdoor unit

 

3-phase outdoor unit

 

 

Indoor Unit

Outdoor Unit

 

Indoor Unit

Outdoor Unit

 

 

B

 

 

B

 

 

 

1

1

 

1

1

 

 

2

2

 

2

2

 

 

Ground

 

 

Ground

 

 

 

4

4

Power supply

4

4

 

Power supply

 

A

 

 

A

 

L

 

 

L1

Inter-Unit

L

Inter-Unit

L1

 

 

 

 

Wiring

 

N

Wiring

 

 

L2

(Line voltage) N

(Line voltage) L2

 

 

 

 

 

 

 

 

L3

 

L3

 

 

 

 

 

 

 

 

Ground

 

N

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

0611_X_S

 

 

 

 

 

 

 

 

 

 

Ground

 

 

 

 

 

 

0612_X_S

3. Check power supply

 

 

 

 

 

Fig. 16

Check that voltage is within the specified range (±10% of the rating).

Check that power is being supplied.

If the following troubleshooting must be done with power being supplied, be careful not to thouch any uninsulated live part that can cause

ELECTRIC SHOCK.

4. Check the lead wires and connectors in indoor and outdoor units.

Check that the sheath of lead wires is not damaged.

Check that the lead wires are firmly connected at the terminal plate.

Check that the wiring is correct.

5Reference

Condition of general cooling operation (Thermo. ON) SWEEP..................ON

Indoor fan speed....HIGH

SM830043