2-2 Freeze Prevention

2. Processes and functions

2-2 Freeze Prevention

Freeze Prevention keeps the indoor heat exchange coil from freezing. Freezing reduces the efficiency of the unit, and frost buildup on the coil blocks cool air circulation from the indoor unit’s fan.

 

FREEZE

 

FREEZE

 

 

PREVENTION

 

PREVENTION

 

MORE THAN 10 MINUTES

6 MINUTES

10 MINUTES

6 MINUTES

 

INDOOR COIL

 

 

 

 

TEMPERATURE

 

 

 

 

–1°C

 

 

(THERMO ON)

 

 

 

 

 

 

 

(THERMO OFF)

 

ON

OFF

ON

OFF

ON

COMPRESSOR

 

 

 

 

ON

OFF

ON

OFF

ON

OUTDOOR FAN

 

 

 

 

SET SPEED

INDOOR FAN

0608_X_S

Fig. 7

2-3 Outdoor Fan Control

In low outdoor temperature, the outdoor fan is set automatically from HIGH to LOW to prevent the indoor heat exchanger from freezing.

When the outdoor temperature falls below 25.5°C, the outdoor fan is set from HIGH to LOW automatically. When the outdoor temperature rises to 27.5°C, the outdoor fan is set from LOW to HIGH automatically.

2

Fig. 8

SM830043

– 31 –