Installation & Service Manual
4Hydronic piping (continued)
Hot water piping must be supported by suitable hangers or floor stands, NOT by the boiler. Copper pipe systems will be subject to considerable expansion and contraction. Rigid pipe hangers could allow the pipe to slide in the hanger resulting in noise transmitted into the system. Padding is recommended on rigid hangers installed with a copper system. The boiler pressure relief valve must be piped to a suitable floor drain. See the relief valve section on page 24 of this manual.
CAUTION | A leak in a boiler system will cause the | |
system to intake fresh water constantly, | ||
| ||
| which will cause the tubes to accumulate | |
| a lime/scale build up. This will cause a | |
|
Water Connections Heating Boilers Only
All water heaters and heating boilers with inputs of 315,000 - 500,000 Btu/hr have 2" NPT.
CAUTION Field installed reducing bushings may decrease flow resulting in boiler noise or
flashing to steam.
Circulator Pump Requirements
This is a low mass, high efficiency hot water boiler which must have adequate flow for quiet, efficient operation. The boiler circulating pump must be purchased locally. The boiler circulator pump must operate continuously while the boiler is firing. Pump selection is critical to achieve proper operation. A pump should be selected to achieve proper system design water temperature rise. A heat exchanger pressure drop chart (Table 4C) is provided to assist in proper pump selection. Also provided is a System Temperature Rise Chart (Table 4B). This table provides GPM and boiler
TABLE - 4C
HEAT EXCHANGER PRESSURE DROP CHART
| 7 |
| CB500 |
|
|
|
|
| |
| 6 |
|
|
|
|
|
| CB360 |
|
| 5 |
|
|
|
FT/HD | 4 | CB | 315 |
|
| CB399 |
|
| |
|
|
|
| |
| 3 |
|
|
|
|
|
|
|
|
2
1
0
0 | 5 | 10 | 15 | 20 | 25 | 30 | 35 |
Gallons per Minute
Circulator Pump Operation (Heating Boilers Only)
Boilers are equipped with a relay for controlling the circulation pump for the hot water loop. The relay turns ON and OFF in response to the “W” input from the wall thermostat or zone control.
The field installed boiler pump MUST NOT exceed 1 h.p. For continuous pump operation, wire the system pump to the 120V supply. The pump should be connected at the junction box as shown in FIG.
120V
SUPPLY
TO
UNIT
Circulator Pump Specifications
1.Maximum operating pressure for the pump must exceed system operating pressure.
2.Maximum water temperature should not exceed nameplate rating.
3.Cast iron circulators may be used for closed loop systems.
4.A properly sized expansion tank must be installed near the boiler and located on the suction side of the pump.
TO
CIRCULATION
PUMP
Figure 4-3_Boiler Wiring - Circulation Pump to Junction Box
27