Pump Wiring for a Heating Boiler

5Electrical connections

Pump Wiring for a Heating Boiler

The heating boiler circulating pump must be purchased locally. The maximum load for the pump switched by the internal pump relay must not exceed 1 HP. The current draw for a field installed 120 VAC pump MUST be added to the boiler’s current draw to determine the minimum wire size for 120 volt service.

TABLE - 5B

AMP DRAW DATA FOR

STANDARD FIRING CODES

 

 

Maximum

Firing Control

Model

Total AMPs /

 

 

120VAC

 

CB 315

.5

M9

CB 360

.5

CB 399

.5

 

 

CB 500

.5

 

 

 

 

CW 90

1.5

 

CW 135

1.5

*F1

CW 180

1.5

CW 199

1.5

 

 

CW 225

1.5

 

CW 270

1.5

 

CW 315

1.5

*F9

CW 360

1.5

CW 399

1.5

 

 

CW 500

1.5

*1.0 AMPs added for “PM” water heaters

IGNITION MODULE

TEMPERATURE

CONTROL

PUMP RELAY

MANUAL RESET

HIGH LIMIT (IF EQUIPPED)

TRANSFORMER

INTERMITTENT PILOT SYSTEM M9 CONTROL PANEL

Figure 5-2_Control Panel Assembly 90-135,000 BTU/hr

Installation & Service Manual

TEMPERATURE

CONTROL

IGNITION

MODULE TABLE - 5B*1.0 AMPs added for “PM” water heatersFigure 5-2_Control Panel Assembly 90-135,000 BTU/hrTemperature AdjustmentOperating Temperature ControlRequirements or Three-Way Valves, seeManual backgroundManual backgroundManual backgroundManual background

PUMP

RELAY

MANUAL RESET

HIGH LIMIT (IF EQUIPPED)

TRANSFORMER

Figure 5-3_Intermittent Pilot System 500,000 Btu/hr Control Panel

Temperature Adjustment

Operating Temperature Control

NOTICE

The temperature controller is pre-set

at the factory with test settings. You

 

 

may need to adjust the settings to meet

 

your specific needs.

 

Return water temperatures must not be

￿ WARNING

less than 140°F. If lower return water

 

temperatures are required, follow the

 

instructions for Low Temperature Bypass

 

Requirements or Three-Way Valves, see

 

page 29.