Installation & Service Manual

Ratings

Copper-fin Specifications

Model Number

 

 

 

 

 

 

Input

Water

Water Connections

Gas Connections

Vent Size

Note: Change “N” to

MBH

Content Gallons

 

 

 

“L” for L.P. gas models

 

 

 

 

(Note 1)

 

 

 

 

 

 

 

 

 

 

 

CWN090

90

.91

2”

1/2”

5”

 

 

 

 

 

 

CWN135

135

.95

2”

1/2”

6”

 

 

 

 

 

 

CWN180

180

.99

2”

3/4”

7”

 

 

 

 

 

 

CWN199

199

1.02

2”

3/4”

7”

 

 

 

 

 

 

CWN225

225

1.02

2”

3/4”

7”

 

 

 

 

 

 

CWN270

270

1.06

2”

3/4”

8”

 

 

 

 

 

 

CWN315

315

1.09

2"

3/4"

8"

 

 

 

 

 

 

CWN360

360

1.12

2"

1"

9"

 

 

 

 

 

 

CWN399

399

1.22

2"

1"

10"

 

 

 

 

 

 

CWN500

500

1.30

2"

1"

10"

 

 

 

 

 

 

NOTICE Maximum allowed working pressure is located on the rating plate.

Notes:

1. Copper-fins require special gas venting. Use only the vent materials and methods specified in the Installation and Service Manual.

2. The Copper-fin is orificed for operation up to 2000 feet altitude. The appliance will be derated 4% per 1000 feet above 2000 feet elevation. Consult the factory for installations above 2000 feet elevation.

UNIT EQUIPPED FOR

HIGH ALTITUDE

UP TO 2000 FT.

Figure B High Altitude Label Location

6

Page 6
Image 6
Lochinvar 500, 90 service manual Copper-fin Specifications