Installation & Service Manual

Ratings

Copper-fin

I=B=R Rating

 

 

 

 

 

Net

Model Number

Input

 

Gross

I=B=R

 

Ratings

 

MBH

 

Output

Note: Change “N” to

 

 

 

MBH

Water,

 

 

 

 

MBH

“L” for L.P. gas models.

(Note 4)

 

 

 

 

 

 

 

 

 

 

 

(Note 1)

(Note 2)

 

Min

 

Max

 

 

 

 

CBN315

158

 

315

258

224

 

 

 

 

 

 

CBN360

180

 

360

295

257

 

 

 

 

 

 

CBN399

200

 

399

328

285

 

 

 

 

 

 

CBN500

250

 

500

410

357

 

 

 

 

 

 

Other Specifications

Boiler Water

Water

Gas

Vent

Content

 

Connections

Connections

Size

Gallons

 

 

 

 

 

 

 

 

(Note 3)

 

 

 

 

1.09

2"

3/4"

8"

 

 

 

 

1.12

2"

1"

9"

 

 

 

 

1.22

2"

1"

10"

 

 

 

 

1.30

2"

1"

10"

 

 

 

 

NOTICE Maximum allowed working pressure is located on the rating plate.

Notes:

1.

The ratings are based on standard test procedures

 

 

prescribed by the United States Department of Energy.

 

2.

Net I=B=R ratings are based on net installed radiation of

 

 

sufficient quantity for the requirements of the building and

 

 

nothing need be added for normal piping and pickup.

 

 

Ratings are based on a piping and pickup allowance of 1.15.

 

3.

Copper-fins require special gas venting. Use only the vent

 

 

materials and methods specified in the Installation and

 

 

Service Manual.

 

4.

The Copper-fin is orificed for operation up to 2000 feet

Figure A High Altitude Label Location

 

altitude. The appliance will be derated 4% per 1000 feet

 

above 2000 feet elevation. Consult the factory for

 

 

installations above 2000 feet elevation.

 

5.

Ratings have been confirmed by AHRI.

 

UNIT EQUIPPED FOR

HIGH ALTITUDE

UP TO 2000 FT.

5

Page 5
Image 5
Lochinvar 90, 500 service manual Ratings, Copper-fin =B=R Rating