FS-8700-43 VESDA Driver Manual

Page 8 of 18

4.4.Client Side Map Descriptors

4.4.1.FieldServer Related Map Descriptor Parameters

Column Title

Function

Legal Values

Map_Descriptor_Name

Name of this Map Descriptor

Up to 32 alphanumeric

characters

 

 

 

Name of Data Array where

One of the Data Array

Data_Array_Name

data is to be stored in the

names from “Data Array”

FieldServer. Only used for

section above. Must be of

 

 

commands 1,4,6,12.

type BIT

Data_Array_Location

Starting location in Data Array

0 to maximum specified in

“Data Array” section above

 

 

 

Function of Client Map

 

Function

Descriptor. A Command is a

RDBC, WRBC, WRBX

 

write, and a response is a read

 

4.4.2.

Driver Related Map Descriptor Parameters

 

 

 

 

 

Column Title

Function

Legal Values

 

 

 

 

One of the node names

 

Node_Name

 

Name of Node to fetch data from

specified in “Client Node

 

 

 

 

Descriptor” above

 

Data_Type

 

Data type

Dig_input or dig_output

 

 

 

 

 

 

Length

 

Length of Map Descriptor

1 to end of data block or less

 

Address

 

Starting address of read block

The start bit number of the data

 

 

of interest

 

 

 

 

 

Command

 

The command id as given in the

1,4,6,10,12,16

 

 

notes.

 

 

 

 

 

Network

 

The network number

1-255

 

Zone

 

The zone number

1-255 or 0 if the Zone is not

 

 

configured on the Panel

 

 

 

 

 

Sector

 

The sector number

1-255 or 0 to read the average

 

 

smoke level and highest alarms.

 

 

 

 

 

 

 

Name of Data Array where data

One of the Data Array names

 

DA_Bit_Name

is to be stored in the FieldServer.

from “Data Array” section above.

 

 

 

Used for command 10 and 16.

Must be of type BIT

 

DA_Bit_offset

Starting location in Data Array.

0 to maximum specified in “Data

 

Used for command 10 and 16

Array” section above

 

 

 

 

 

 

Name of Data Array where data

One of the Data Array names

 

DA_Float_Name

is to be stored in the FieldServer.

from “Data Array” section above.

 

 

 

Only used for command 10.

Must be of type FLOAT

 

DA_Float_offset

Starting location in Data Array.

0 to maximum specified in “Data

 

Only used for command 10

Array” section above

 

 

 

 

 

 

Name of Data Array where data

One of the Data Array names

 

DA_Byte_Name

is to be stored in the FieldServer.

from “Data Array” section above.

 

 

 

Only used for command 16.

Must be of type BYTE

 

DA_Byte_offset

Starting location in Data Array.

0 to maximum specified in “Data

 

Only used for command 16

Array” section above

 

 

 