4.Configuring the FieldServer as a VESDA Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Vesda Server.

4.1.Data Arrays

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Vesda communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

 

Section Title

 

 

 

Data_Arrays

 

 

 

Column Title

Function

Legal Values

 

Data_Array_Name

Provide name for Data Array

Up to 15 alphanumeric

 

characters

 

 

 

 

Data_Format

Provides data format

BIT,FLOAT,BYTE

 

Data_Array_Length

Number of Data Objects

1-10000

 

 

 

 

 

Example:

 

 

 

 

 

 

 

// Data Arrays

 

 

 

Data_Arrays

 

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length

 

set_op,

bit,

32

 

VESDA01_1_f,

float,

32

 

VESDA01_1_b,

bit,

32

 

VESDA01_2_f,

float,

32

 

VESDA01_2_b,

bit,

32

 

VESDA01_3_f,

float,

32

 

VESDA01_3_b,

bit,

32

 

VESDA01_4_f,

float,

32

 

VESDA01_4_b,

bit,

32

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com