FieldServer FS-8700-43 instruction manual VESDA data format for command 12 Current Fault Status

Models: FS-8700-43

1 18
Download 18 pages 14.68 Kb
Page 13
Image 13
4.5.4.VESDA data format for command 12 (Current Fault Status)

FS-8700-43 VESDA Driver Manual

Page 13 of 18

4.5.4.VESDA data format for command 12 (Current Fault Status)

This request returns the Current Fault Status in a BYTE data array. The format for the data is as follows:

Data Arrays

 

Column Title

 

Function

 

Legal Values

 

Data_Array_Name

 

Provide name for Data

 

Up to 15 alphanumeric

 

 

Array

 

characters

 

 

 

 

 

Data_Format

 

Provides data format

 

BYTE

 

Data_Array_Length

Number of Data Objects

 

1 – 21

 

 

 

 

 

 

Client Side Map Descriptors

 

 

Column Title

 

Function

 

Legal Values

 

 

 

Map_Descriptor_Name

 

Name of this Map

 

Up to 32 alphanumeric

 

 

 

 

Descriptor

 

characters

 

 

 

 

Name of Data Array where

 

 

 

 

 

Data_Array_Name

 

data is to be stored in the

 

As above.

 

 

 

 

FieldServer

 

 

 

 

 

Data_Array_Location

 

Starting location in Data

0

 

 

 

 

Array

 

 

 

 

 

 

 

 

 

 

Function

 

Function of Client Map

 

RDBC

 

 

 

Descriptor.

 

 

 

 

 

 

 

 

 

 

 

 

Name of Node to fetch data

 

One of the node names

 

 

Node_Name

 

 

specified in “Client Node

 

 

 

from

 

 

 

 

 

 

Descriptor” above

 

 

 

 

 

 

 

 

 

Data_Type

 

Data type

 

dig_input

 

 

Length

Length of Map Descriptor

 

1-21 (must not overflow the

 

 

 

data array)

 

 

 

 

 

 

 

 

 

Address

 

Starting address of read

0

 

 

 

 

block

 

 

 

 

 

 

 

 

 

 

Command

 

The command id as given in

12

 

 

 

 

 

the notes.

 

 

 

 

 

Network

 

The network number

1-255

 

 

 

Zone

The zone number

1-255

 

 

 

Sector

 

The sector number

1-255

 

Data Block Description5

 

 

 

 

 

 

 

 

BYTE offset

 

 

Function

 

 

0

 

 

Number of faults

 

 

 

 

1 - 20

 

 

Fault list

 

 

 

51 indicates TRUE; 0 indicates FALSE

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Page 13
Image 13
FieldServer FS-8700-43 VESDA data format for command 12 Current Fault Status, 5 1 indicates TRUE 0 indicates FALSE