Driver Manual

4.2Client Side Connections

Section Title

 

 

 

 

Connections

 

 

 

 

Column Title

 

Function

 

Legal Values

Port

 

Specify which port the device is

 

P1-P8, R1-R2

 

 

connected to the FieldServer

 

(P1-P8) requires 232/485

 

 

This is the port connected to the

 

converter.

 

 

 

 

 

 

DART’s RS232 port.

 

 

 

 

 

 

 

Secondary_Port*

 

Using a Dart ? Do not specify

 

P1-P8, R1-R2

 

 

this parameter.

 

(R1-R2) requires 232/485

 

 

 

 

converter.

Baud*

 

Specify baud rate

 

2400 (Others available but

 

 

 

 

Daire only operates at 2400

 

 

 

 

baud.)

Parity*

 

Specify parity

 

None

Data_Bits*

 

Specify data bits

 

8

 

 

 

 

 

Stop_Bits*

 

Specify stop bits

 

1

 

 

 

 

 

Protocol

 

Specify protocol used

 

Dart

 

 

Either keyword may be used.

 

 

Handshaking*

 

Specify hardware handshaking

 

None

Poll Delay*

 

Time between internal polls

 

0-32000 seconds

 

 

 

 

default 1 second

Example

 

 

 

 

//Client Side Connections

Connections

 

 

 

 

Port, Parity, Data_Bits, Stop_Bits,

Protocol, Poll_Delay

P1,

2400 , None,

8,

1,

Dart

, 0.100s

FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042

Visit our website: www.fieldserver.com E-mail: support@fieldserver.com

Page 6

Page 8
Image 8
FieldServer FS-8700-78 Driver Manual Client Side Connections Section Title, Using a Dart ? Do not specify, None